Card Installation - Honeywell Vigilon 4 loop Generic Commissioning Instructions

Fire panels & network nodes
Table of Contents

Advertisement

Card installation

Backplane
40 way ribbon
20 way ribbon
Master Controller Card (MCC)
to be fitted to socket
P1 CARD 0 on backplane
P1
CARD 0
P2
CARD15
P3
CARD 1
P4
CARD 2
P5
CARD 3
P6
CARD 4
P7
CARD 5
P8
CARD 6
Backplane
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Secure the two ribbon
cables (at the fold) under the clamp
located on the backplane
Card guides
Use the USB port on
the MCC to connect to
the Commissioning tool.
Main Controller Card
(SUPPLIED)
Network or IO Card (Optional)
Loop Processor Card (SUPPLIED)
or RS232
Loop Processor Card or RS232
(Option)
Loop Processor Card or RS232
(Option)
Loop Processor Card or RS232
(Option)
Fibre Network or RS232 or
Loop Card#
Network or RS232 or
Loop Card#
# for VIG1-72 only
Vigilon 4/6 loops & Compact (VA) panels & network nodes
&
When installing cards into the backplane always use anti-static work
procedures. DO NOT use anti-static procedures on live equipment.
"
An IO Card is not required for connection to DKC and neither is it required to
connect to the Commissioning tool. The DKC now connects directly to the MCC card. The
Commissioning tool connects directly to the USB port on the MCC.
The two ribbon cables held together under a masking tape on the DKC assembly must be routed
into the backbox to connect to the Main Controller Card.
"
Ensure the two ribbon cables from DKC are secured under a clamp on the
backplane. Fit the Main Controller Card (MCC) into the backplane before the ribbon
cables are connected to the MCC.
&
Always ensure the panel is completely powered down before removal
or fitting of cards into the backplane. Power down the battery supply before the
mains supply. The power up should be done in reverse order.
¨
Ensure all the cards are installed in their correct location into the backplane and are
firmly seated into their respective slots.