34000 range of sensors STATES (legacy devices)

&
The release of control panel software (MCC/MCB equal to or greater than V4.41):
If a non defined STATE is selected during commissioning then the control panel will revert to STATE 0.
The previous release of control panel software (MCC/MCB less than V4.41)
If a non defined STATE is selected during commissioning then the control panel will revert to STATE 15, which means the device is functionally switched OFF.

Optical heat sensor (plus sounder) STATES (34000 range)

These STATES cover the following sensors:
¨
Optical & heat sensor
¨
Optical & heat sensor plus sounder
¨
Heat sounder
For the Heat sounder product range ignore the Optical STATES.
STATES
Definition
State 0 (LPC approved)
Heat Grade 2
Optical smoke normal sensitivity
State 1
High sensitivity optical
Grade 2 heat
State 5
Medium sensitivity optical only
State 8 (LPC approved)
Medium sensitivity optical with
20 seconds time constant
Grade 2 Heat
State 10
Medium sensitivity optical with time
delay (20 second time constant) or
Grade 2 heat
State 11
Low sensitivity optical
Grade 3 Heat
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Vigilon 4/6 loops & Compact (VA) panels & network nodes
Application
Suitable for most applications. Provides smoke detection to meet BS5445:Part 7 and
provides heat detection to meet Grade 2 as defined in BS5445:Part 5.
Used in areas or situations where airborne smoke or dust is unlikely to occur and therefore
a more sensitive detection is available.
Where high ambient temperatures of greater than 40
This state is useful in hotel bedrooms where low levels of signals could occur for short
durations. If smoke and heat occur simultaneously, the time delay is effectively overridden
to provide fast detection.
Similar performance to state 8 but without the time delay overridden. Useful in hotel
bedrooms and loading bays where low levels of signals may occur.
Used for smoke detection in areas where airborne particles or smoke is normally present,
o
or high temperatures (up to 40
C) can be normally attained.
o
C are expected in the detection area.