Honeywell Vigilon 4 loop Generic Commissioning Instructions page 132

Fire panels & network nodes
Table of Contents

Advertisement

Commissioning instructions
Message
associated with..
NVM
NVM is read only
(non volatile memory)on
backplane or MCB
Panel in/out of
MCC / MCB
(main control card/board)
commissioning mode
MCC / MCB
Panel Label Set up
(main control card/board)
Panel powerup
MCC / MCB
(main control card/board)
LPC
Pattern number x on
loop y channel x
(loop processor card)
Any Card
Pointer corrupted at
card x
Any Card
Pointer missing at
card x
Prefire number x on
LPC
loop y channel z
(loop processor card)
MCC / MCB / DAC / MRC
Printer lost/fitted
at card x number y on
loop z
Program memory
Any Card
corrupted at card x
132
meaning..
User attempts to write to a hardware write protected
NVM
Commissioning mode switched ON/OFF.
Panel label has been set from the menu.
Software reset of system or there has been a manual
reset of card 0.
Sensor has detected an interesting event eg fire/fault.
Software error.
Software error
Pattern match less than a Fire.
The external printer has not been seen and is 'lost'.
Checksum failure on FLASH at midnight.
..possible action
Remove the hardware write protect before
writing
To manually switch commissioning mode use
the [test/eng] menu.
-
If an automatic reset has occurred then check
for system errors.
-
Software errors will activate a system reset.
Ignore single occurrence.
Record the event in the log book.
Software errors will cause a system reset.
Card fault should be ignored for single
occurrence.
Record the event in the log book.
-
Check the connections to the printer.
check for paper jam in the printer
Clear and ignore single occurrence.
Record in the log book.
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Also
mechanism.