Commissioning instructions

Settings on the DKC

The links and pot on the DKC are factory configured as shown below.
This link is used
for keyswich application
only. Leave link fitted.
Control buttons
Sound Alarms
Factory setting
is with link fitted
Buttons
Verify
enabled
Reset
Buttons
Silence Alarms
disabled
38
LCD Contrast adjust
Anti-Clockwise -
Lighter
RV1
Clockwise -
Darker
RV1
Display and
keyboard Card (DKC)
Inner door
With Zone
indicators
(EN)
1
2
3
Zones
17
18
19
Without Zone
indicators
Network node
Control buttons
&
The emergency control buttons MUST always be left in an enabled state, with the
'control buttons' link fitted.
There is no indication given at the panel when the links are set for inactive
controls.
Display Contrast
¨
The display contrast is set using the Pot RV1 on the DKC, which is factory adjusted
for optimum contrast. You can also adjust the contrast using the menu option under
[Test/Eng].
"
P1
The contrast adjustment function using the menu options may not be
applicable for some older build of panels.
P6
Address and baud rate
"
The node and domain addresses can be changed from the factory settings to
a required address using the panel [Test/Eng] menus.
Zone indicators
The Zone indicators are enabled for normal operation at the control panel and must NOT be
disabled.
The Zone indicators are not applicable for a Network node or BS panel so the zone indicator links
4
are set in the disabled position.
20
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.