Honeywell Vigilon 4 loop Generic Commissioning Instructions page 137

Fire panels & network nodes
Table of Contents

Advertisement

Message
associated with..
Panel's Serial Link
Voice Alarm comms
failed
Port 1 / Node x
Panel's Serial Link
Voice Alarm comms
failed
Port 1 / Node x
Connected D1 Voice Alarm
Voice Alarm common
system
fault Node x
Voice Alarm
Configuration fault at a D1
Voice Alarm System
configuration fault
Nos. 17
MCC / MCB
Warm restart
(main control card)
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Vigilon 4/6 loops & Compact (VA) panels & network nodes
meaning..
There is a serial link wiring fault between Vigilon
panel 'Port 1' and DOM/Comprio. Other Vigilon panels
in the connected network will indicate the 'Node'
number of the panel connected to DOM /Comprio.
There is a serial link wiring fault has been restored
between Vigilon panel 'Port 1' and DOM/Comprio.
Other Vigilon panels in the connected network will
indicate the 'Node' number of the panel connected to
DOM /Comprio.
There is a common fault, that is any fault in D1 Voice
Alarm system, for example Speaker line fault,
Amplifier fault, Mains power fault, etc.
The ERROR LED is lit at the DOM/Comprio
connected via serial link to Vigilon panel.
This message and indication is given at Vigilon panel
of a configuration fault in a D1 Voice Alarm system.
The affected output (VOP) in this case No 17 is not
recognised.
The 5V rail has seen a dip activating the watchdog or
the button has been pressed on MCC / MCB or panel
power reconnected.
..possible action
Check the serial link is working, ensure:
¨
Serail link cable is connected to DOM to
socket TWI
¨
Serial link cables are connected to the two 9
way D Type connectors on the Adapter
TWI-RS232 and
¨
Serail link cable is wired correctly at a
Vigilon/Compact panel to terminals Tx, Rx
and 0V.
-
Find the cause of common fault at a D1 Voice
Alarm system:
¨
Refer to user guides for D1 Voice Alarm
system modules to locate the fault.
¨
Once the fault is rectified the fault message
and notice fault indications are removed at
both Vigilon and D1 Voice Alarm system.
Test for a configuration error which occurs
when a non existent or not configured properly
Virtual Output Point is made active.
¨
Confirm the VOP displayed as being faulty is
non existent.
¨
Rectify the configuration at Vigilon and/or at
the D1 Voice Alarm system.
¨
Repeat this test to ensure the revised
configuration works. Check to ensure the
fault has cleared.
-
137