Commissioning instructions
Wiring a Copper network
From
previous
panel
or node
No
connection
0V1 +VE1 -VE1 0V2 N/C +VE2 -VE2 N/C
Connections for
Network card in
Socket P8 (Card 6)
(post 08-2006)
BACKPLANE
Control Panel
Wiring a Fibre network
Side 2
Side 1
Rx
(End 2)
(End 1)
Tx
P7
P4
P6
P5
Rx
Tx
Rx
Tx
P2
P3
BACKPLANE
Control Panel
Links P2 and P3 are booster links.
Normally the links are not fitted, however for
distance exceeding 750m the links must be fitted.
90
Cable screen
N/C
P10
P10
0V1 +VE1 -VE1 0V2 N/C +VE2 -VE2 N/C
Connections for
Network card in
Socket P8 (Card 6)
(post 08-2006)
BACKPLANE
Control Panel
Side 2
Side 1
(End 2)
(End 1)
P7
P4
P6
P5
Rx
Tx
Rx
Tx
P2
P3
BACKPLANE
Control Panel
P10
1
2
3
4
5 6
7
8
0V -ve +ve 0V I -ve +ve |
Connections for
Network card in
Socket P8 (Card 6)
BACKPLANE
(Pre 08-2006)
OLD Legacy Control Panel
Tx
Rx
0V L2- L2+ 0V L1- L1+
Connections for
Network card in
Socket Card 2 of MCB
Compact Control Panel
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
To Next
panel
or node