Honeywell Vigilon 4 loop Generic Commissioning Instructions page 14

Fire panels & network nodes
Table of Contents

Advertisement

Commissioning instructions
LPCB approved S-Quad Sensor with VAD device STATES
# - factory default settings
Device
Dual Optical & Heat sensor variant -
(With VAD)
(With VAD)
(With VAD)
(With VAD & Speech)
(With VAD & Speech)
Dual Optical, Heat & CO sensor variant-
(With Speech & VAD)
(With Speech & VAD)
Optical & Heat sensor variant -
(With Sounder)
Heat sensor variant -
(With Speech & VAD)
(With Speech & VAD
Optical sensor -
All S-Quad range of sensor sounder devices meet EN54-17:2005 Input/Output devices plus EN54-18:2005 Short circuit isolation for use on the transmission path of fire detection and alarm systems.
Sounder tone - Meets the following tone settings: High tone ( Continuous 933Hz) & Alternate tone (High 933Hz for 0.25s / low 700Hz for 0.25s)
When an S-Quad sensor is configured to operate a non LPCB approved STATE then this will contravene the LPCB approval.
# - these standards are met when the sensor is operating LPCB approved STATES.
All the LPCB approved STATES applicable to S-Quad fire sensors are shown. The required STATE is configured during commissioning. On initial power-up of the system all the sensors operate in
STATE 0.
Note sensor STATES are not applicable for wireless sensors.
14
LPCB approved STATE
S4-711
STATE 0 #
S4-711-VAD-HPR
STATE 5
S4-711-VAD-LPW
S4-711-VAD-HPW
STATE 8
S4-711-V
(With Speech)
S4-711-V-VAD-HPR
S4-711-V-VAD-HPW
S4-771-S
(With Sounder)
S4-901
STATE 0 #
S4-911-V-VAD-HPR
STATE 9
S4-911-V-VAD-HPW
S4-710
STATE 0 #
S4-770-S
S4-720
STATE 0 #
S4-720-V-VAD-HPR
STATE 5
) S4-720-V-VAD-HPW
S4-780-S
(With Sounder)
State 0 #
S4-715
Meets ~ EN54-7 : 2000, A1:2002, A2:2006
* EN54-5 : 2000, A1:2002
Medium optical smoke ~ / Class A1 heat *
Medium optical smoke ~ / Class B heat *
Delayed medium optical smoke ~ / Class A1 heat*
Medium optical smoke ~ / Class A1 heat *
Class A1 heat *
Medium optical smoke ~ / Class A1 heat*
Class A1 heat *
Class B heat *
Medium optical smoke
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.