Non Volatile Memory (Nvm); Nvm Hardware Write Protect - Honeywell Vigilon 4 loop Generic Commissioning Instructions

Fire panels & network nodes
Table of Contents

Advertisement

Non Volatile Memory (NVM)

The NVM is located inside the panel on the Backplane of VIGILON panel and on the
Master Control board of VIGILON Compact (VA) panels. The NVM should hold
the latest system configuration data.
&
Do not attempt to write protect using the link P13 while a back up
to the flash chip or initialisation of the memory is in progress.
The link header P13 on the Backplane provides hardware 'write' protection and will stop
[Save] and [Back-up] commands from the panel controls modifying the memory. The link is
factory fitted to allow card data to be saved to the NVM.
"
Where the system is required to be EN54 Part 2 compliant, then the link
P13 must be left in protect enabled position, that is to disallow write to NVM, on
completion of system commissioning.
.
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Vigilon 4/6 loops & Compact (VA) panels & network nodes

NVM Hardware Write protect

Hardware 'write protect' on a VIGILON 4/6 loop panel
New Vigilon
4/6-loops panel
P13
LK1
Protected
- Write protected
Unprotected
- NOT write protected
(factory setting)
Backplane
Hardware 'write protect' - VIGILON Compact & (VA) panels
New Master Control Board (MCB) - networkable
24V
0V
B
A
L1 0V L2 0V
NC C NO NC C NO NC C NO
L1 0V L2 0V
0V MIPNC C NO
TX1 RX1 0V
TX2 RX2
PB15
PB6
PB14
PB10
PB11
PB7
PB9
24V
MA1 - FS1 250mA
FS3 200mA
MA2 - FS2 250mA
P1
CARD 2
P2
CARD 1
FIRMWARE BACKUP
IC3
IC16
SW2
MODE
P13
P16
SW1
RESET
Insulation Disk
Non Volatile
'Hardware' NVM protect link P13 is factory set to NVM protect disabled
Memory -
NVM
NVM protect - [Disabled]
(ie NVM unprotected,
that is
write allowed
)
Older Vigilon
TERMINALS
FOR CARD IN P8
4-loops panel
1 2 3 4 5 6 7 8
TERMINALS
FOR CARD IN LOOP 5
1 2 3 4 5 6
Backplane
IC2
IC1
P13
P13
P13
Write protected
NOT Write protected
(factory setting)
OLD Master Control Board (MCB) - non networkable
MA1+ MA1- MA2+ MA2-
PB8
P15
P10
P11
P6
P14
P7
24V
MA2 - FS2 250mA
FS3 200mA
MA1 - FS1 250mA
P1
CARD 2
P2
CARD 1
BATT1
CODE
BCKUP
POWER
SUPPLY
P12
IC3
IC16
P16
SW1
P13
BATT3
NVM protect - [Enabled]
There is also 'software'NVM
(ie NVM protected,
protect enable and disable
that is
write not allowed
)
feature, see menu maps.
P9 P8
POWER
SUPPLY
P12
59