Condition Codes For S-Quads (Exception / Sub Fault Codes) - Honeywell Vigilon 4 loop Generic Commissioning Instructions

Fire panels & network nodes
Table of Contents

Advertisement

Condition Codes for S-Quads (Exception / Sub Fault codes)

Gen
Pos.
type
No.
Description
1
Optical subfire
E
N
V
2
Heat subfire
I
O
R
3
Gas subfire
N
M
E
4
Beam
N
T
5
Optical/Gas channel drift or out of
range
S
6
Heat channel drift or out of range
E
N
S
7
Optical/Gas channel noisy
O
(High freq)
R
8
Heat channel noisy (High
frequency)
D
9
device firmware
E
V
I
10
device transmission
C
E
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Vigilon 4/6 loops & Compact (VA) panels & network nodes
Normal
band
0
1
None
Small signal sensed
[Check location, state & type]
None
Small signal sensed
[Check location, state & type]
-
Small signal sensed
[Check location, state & type]
OK
-
OK
OK
OK
Single HF noise event
detected
OK
Single HF noise event
detected
OK
Isolated fault
[Note/report]
OK
Low error rate
Condition codes
Sub fault band
2
Subfire
[Check location, state & type]
Subfire
[Check location, state & type]
Subfire
[Check location, state & type]
-
Close to acceptable limit
Multiple HF noise seen
(Check location and report)
Multiple HF noise seen
(check location and report)
Repetitive fault
[Note / report / replace]
Medium error rate
[Report]
Fault band
3
Obscured for > 1min or Tx
failure
Out of limits
[Clean/replace]
Out of limits
[Clean/replace]
Total failure
[Replace]
High error rate
[Replace]
71