Honeywell Vigilon 4 loop Generic Commissioning Instructions page 127

Fire panels & network nodes
Table of Contents

Advertisement

Message
associated with..
Device
Interface input not
Reset number x on
loop y channel z
Interface Input OC /
Device
restored
Device
Interface input
operated / released
number x on loop y
channel z
Device
Interface input SC /
restored number x on
loop y channel z
Interface output SC
Device
or OC or Restored
number x on loop y
channel y
Intermittent Fault at
Any Card
card x
LPC
Invalid configuration
(loop processor card)
Device
Invalid configuration
LPC
at card x
(loop processor card)
LPC
Invalid message /
reply received at
(loop processor card)
card x
Network Card
Invalid message/reply
at card x
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Vigilon 4/6 loops & Compact (VA) panels & network nodes
meaning..
The input line continues to trigger.
The end-of-line is not seen.
Fixed extinguishant interface unit input has been
triggered (applicable for old systems only).
The interface wiring is short circuit. The value of input
is equal to or less than 2V.
The value of output is equal to or less than 50% for SC
or is TBA for OC.
A fault has been picked up by the MCC / MCB (main
control card/board).
Loop recovered with freeblocks ON.
FLASH incorrectly programmed
Loop recovered with freeblocks ON
or Loop
configuration faulty, possibly after upload from
Commissioning
Tool.
The message/reply received cannot be understood. The
communication can be from a Repeat, Mimic,
Networked system.
The message/reply has not been understood from other
panels.
..possible action
Check devices on the IO line.
Check the wiring. The device may have been
removed, if so refit the device to restore.
Follow the FE system reset procedure to release
the input.
Check the interface wiring and rectify to restore
the input.
Check the wiring and restore the output circuit.
Replace the appropriate card if the fault keeps
reoccurring.
This is not allowed. Switch OFF the freeblocks
and reallocate.
Replace the device
This is not allowed. Switch OFF the freeblocks
and reallocate.
Ignore single occurrence and record in the log
book.
Ignore for single occurrence and record in the
log book.