Time slots and Time blocks

MAXIMUM OF 16 PER PANEL
ACTION
TIMESLOT 1
ENABLE / DISABLE TIMESLOT
COMMAND
BUILD
0 - 24 hrs
DELAYED BY
ENABLE TIME
08:00
DISABLE TIME
17:00
TIME
AND/OR
AND
OR
DAYS SETUP
(BOTH)
(EITHER)
DAYS
MON
TUE
:
THU
FRI
SAT
NOTE: A Timeblock may contain any multiple Timeslots.
A Timeslot may be linked to any number of Timeblocks.
The default is for all the devices to be in Time block 0.
A Timeblock is enabled if any one of the Timeslots within
it is in the enable state.
Time slots
A Time slot must be linked with a Time block. It is the Time block that perform actions on the system.
"
Timeslots do not process when the panel is in a fire condition.
¨
a Time slot can be:
triggered automatically
switched ON / OFF manually
or switched ON / OFF by Command build
¨
it performs an action immediately or after a delay of 0 to 24 hours.
¨
There can be up to 16 Time slots per panel
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
MAXIMUM OF 15 PER PANEL
TIMEBLOCK 1
SETUP
TIMESLOT 1
TIMESLOT 2
TIMESLOT 3
TIMESLOT 4
WED
SUN
TIMESLOT 16
Vigilon 4/6 loops & Compact (VA) panels & network nodes
¨
¨
SETUP
Zone
¨
DEVICE NO. = "X"
SETUP
ENABLE STATE
0
¨
DISABLE STATE
15
DEVICE NO. = "X"
SETUP
ENABLE STATE
8
DISABLE STATE
13
Time blocks
A Time block is used to perform periodic enable disable action on
COMMAND BUILD NO. "Y"
TRIGGER
the system.
¨
A COMMAND BUILD LINKED
TO A TIMEBLOCK WILL BE
TRIGGERED WHEN THE
TIMEBLOCK IS ENABLED
AND REVERSED WHEN THE
¨
TIMEBLOCK IS DISABLED.
¨
¨
¨
¨
¨
each Time slot has to be given an Enable time and a
Disable time
each Time slot must be ANDed / ORed to the days of
week, (Mon, Tue, Wed, Thu, Fri, Sat, Sun).
when a Time slot is ANDed with selected days, it will
only operate on the selected days
when a Time slot is ORed with selected days, it will be
Enabled during selected times and will remain ON
throughout the days selected.
There are 0 - 15 Time blocks per panel
the Time block 0 is always in the Enable state and is the
default for all sensors
a Time block can be linked to one or more Time slots
when a Time slot is enabled the time block it is linked to
is also Enabled
a sensor or interface input can only be assigned to one
Time block
when a Time block is in an Enable state:
any sensor(s) linked to it will operate in the Enable
state that has been set up
any Command build linked to it is triggered.
when a Time block is in a Disabled state any Zone tasks
linked to it are also Disabled.
149