Honeywell Vigilon 4 loop Generic Commissioning Instructions page 121

Fire panels & network nodes
Table of Contents

Advertisement

Message
associated with..
MCC / MCB
Clock changed / Clock
(main control card/board)
not set up
CO sensor faulty
Device
CO sensor near end of
Device
life
Device
CO sensor restored
MCC / MCB
Command build
activated /
(main control card/board)
deactivated
MCC /MCB
Command build enabled
(main control card/board)
/ disabled
MCC / MCB
Comms enabled /
disabled at card x
(main control card/board)
Network Card
Network node
Comms Supply Fault
Comms supply Restored
Network node
MCC / MCB
Communications
(main control card/board)
started / stopped at
card x
Network
Control passed
at
card x
Any Card
Corrupted NVM memory
at card x
Power supply
DC Power fail /
restored
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Vigilon 4/6 loops & Compact (VA) panels & network nodes
meaning..
Time and date has been altered or no time has been
entered.
There is a fault with the CO sensor in an S-Quad.
The CO cell is nearing the end manufacturer
recommended life expectancy in an S-Quad.
The CO sensor fault has been restored in an S-Quad
Command build has been switched ON (activated) or
switched OFF (deactivated).
This is an automatic or manually controlled action.
Card communications have been enabled or disabled.
Control panel has been isolated from the network.
The communications power supply has failed.
The communications power supply has been restored.
Communication to a particular panel or to external
equipment linked to the panel (eg Laptop having the
commissioning tool) has started / stopped.
-
Checksum failure on configuration at midnight.
The ADC of output 27V regulator is
normally=146(28.5V).
..possible action
If necessary, set the clock using the set up
menu.
Replace device
Replace the device
-
If necessary switch ON/OFF the command
build using the [control] menu.
If necessary, manually enable/disable the
command build using the [control] menu.
If necessary, manually enable/disable the
Comms using the [control] menu
Replace the power supply unit.
-
Check the wiring.
-
Recover data and record event in the log book.
If it reoccurs then replace the card.
-
121