Honeywell Vigilon 4 loop Generic Commissioning Instructions page 120

Fire panels & network nodes
Table of Contents

Advertisement

Commissioning instructions
Message
associated with..
Device
Call point open cct
number x on loop y
Call point
Device
operated/restored
number x loop y
Device
Call point short cct
number x loop y
Card found/lost at
Any Card
card x
NVM
Card n recovered
(non volatile memory) on
/Card n backed up
backplane or MCB
Chamber Removed
Device
/Replaced number x on
loop y
Panel
Charger Fault
Power Supply Unit (PSU)
EN54 System device power
Charger Fault
supply
number x on loop y
(Repeat, Mimic or mains
powered interface)
Charger Restored
Panel power supply
EN54 System device power
Charger Restored
supply
number x on loop y
(Repeat, Mimic or mains
powered interface).
Chk=4.874 NVMC 41874
NVM
(non volatile memory) on
Flag=0
backplane or MCB
NVM is write
protected at Card x
120
meaning..
Monitored base does not see end-of-line unit. There is
a bad connection to MCP.
Break glass has been broken or operated with a test
key.
Call point contacts are short circuit.
The card has been found/lost. If lost then it is locked
out.
Data recovered to a card from the NVM. A card data
has been backed up to the NVM.
Device chamber has been removed.
Charger circuit has failed.
Charger circuit has failed at a loop device.
Charger circuit is working again.
Charger circuit at the loop device is working again.
The memory is read only.
..possible action
Check the internal wiring, there may be a loose
connection.
Replace the break glass to restore the call point
or remove the test key, whichever is applicable.
Check the call point contacts and internal
wiring.
There may be a hardware fault on card or
backplane. Investigate and rectify.
-
Replacing the chamber will cause a replaced
indication.
Replace the PSU.
Replace the board (having the power supply) on
the loop device.
-
-
Disable the write protect using the [set up]
menu.
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.