Terminals On The Master Control Board (Mcb) - Honeywell Vigilon 4 loop Generic Commissioning Instructions

Fire panels & network nodes
Table of Contents

Advertisement

Terminals on the Master Control Board (MCB)

NC C NO NC C NO
PB10
AUXILIARY RELAY 1
L1 0V L2 0V
PB14
LOOP 2
TX1 RX1 0V TX2 RX2
PB6
RS-232
24V
0V
B
A
PB15
REPEAT
24V
0V
B
A
TX1 RX1 0V
TX2 RX2
L1 0V L2 0V
NC C NO NC C NO NC C NO
INDICATOR
PB10
PB15
PB6
PB14
RS-485
24V
FS3 200mA
P1
CARD 2
FIRMWARE BACKUP
IC3
IC16
SW2
MODE
P16
Master Control Board
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
NC C NO
PB11
AUXILIARY RELAY 2
L1 0V L2 0V
PB7
LOOP 1
0V MIPNC C NO
PB9
MONITORED INPUT
and CLEAN CONTACTS
MA1+ MA1- MA2+ MA2-
PB8
L1 0V L2 0V
0V MIPNC C NO
MA1+ MA1- MA2+ MA2-
MASTER ALARMS
PB11
PB7
PB9
PB8
MA1 - FS1 250mA
MA2 - FS2 250mA
P2
CARD 1
POWER
SUPPLY
P12
SW1
BATT3
RESET
Vigilon 4/6 loops & Compact (VA) panels & network nodes
Descriptions of MCB terminals
Terminals
Description
24V, 0V, B and A
These terminals accept the connection of a repeat indicator
panel (Port 0). Also the power terminals may be used on a
Network node to supply BACnet Gateway.
NC, C and NO
These are auxiliary relay contacts. The auxiliary relay 1 is
Aux 1- 2-sets
normally de-energised and operates with any fire event. The
auxiliary relay 2 is normally energised and operates
Aux 2 - 1set
(de-energises) with any fault event.
0V, TX, A, RX
These are terminals for RS232 or RS485 (Port 1 or 2
and B
respectively).
L1, 0V, L2, 0V
These terminals accept the connection of system devices on
(Loop 1 and
a loop circuit that starts at L1 and ends at L2. Devices that
Loop 2)
are connected to the loop circuit include addressable fire
sensor/sounders, manual call points, interface units and
repeat/mimic panels.
MA1+, MA1-,
These terminals can accept two master alarm circuits that
MA2+ and MA2-
can operate 24V conventional alarm devices.
0V and MIP
These are monitored input terminals that can accept the
connection of a switch. An active input will trigger Command
build 250.
NC, C and NO
These are voltage free relay contacts (output) that operate
(clean contact)
with a fire event.
37