Master Groups - Honeywell Vigilon 4 loop Generic Commissioning Instructions

Fire panels & network nodes
Table of Contents

Advertisement

Commissioning instructions

Master Groups

PANEL 1
MASTER GROUP 1
MASTER GROUP 2
MASTER GROUP 3
OUTPUT
RESET
MASTER GROUP 4
MASTER GROUP 5
MASTER GROUP 6
BOTH
SILENCE
MASTER GROUP 7
ALARMS
MASTER GROUP 8
¨
There can be up to a maximum of 8 Master Groups per network.
¨
These are a collection of Groups used for:
selective fire and non fire event message routing within a Control Panel or around a Network
of Panels
and for routing Global Controls 'Silence Alarms, Sound Alarms and/or Reset' to designated
Control Panels in a Network.
¨
Messages can be displayed or printed on Control Panels and Repeat Panels. Messages are routed
on a Card by Card basis, ie:
Card 0 = Panel LCD
Card 15 on Vigilon panel (Card 0 on Vigilon Compact panel) = Panel Printer
Cards 1-6 = Repeats and Mimics panels on Loops 1-6
Each Card can be configured to display/print All Events (default) or just Fire Events.
Repeat Panels on the same loop will always give the same information.
160
"
PANEL 2
indication, the local panel will also have to route reset messages to other
groups, besides Group 0.
¨
LINK
MCC / MCB
Groups within different Control Panels can be assigned to the same
CARD 0
Master Group
¨
Global controls can be configured to output/input or both.
¨
Messages and controls within a standalone system do not require any
setting up
¨
INPUT
the Group 0 contains all panel events and fire resets and therefore must
RESET
always be assigned to a Master Group.
"
operate globally, like the Sound alarms, Silence alarms and Reset buttons.
BOTH SILENCE
ALARMS
Once message passing has been setup for global repeat or mimic
The Verify control button is applicable for EN panels only can
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.