Psu Led Indications; Write Protect Link On Backplane - Honeywell Vigilon 4 loop Generic Commissioning Instructions

Fire panels & network nodes
Table of Contents

Advertisement

PSU LED indications

Ribbon cable
to Terminal Card
connector P10
Spade connector
for 0V lead to printer
Ribbon cable to
Flashing indication
connector P12
Steady indication
LD2
ERROR
RAM write/read
test failed
ROM checksum error
EEPROM checksum error
EEPROM stuck in
busy mode
EEPROM reinitialised
EEPROM read does
not match RAM copy
The above LEDs flash 1s on and 1s off.
When a LED is ON it indicates an error.
For more than one error the LEDs will flash in sequence.
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
PSU
LD1
LD2
LD3
LD4
LD5
Backplane
LD5
LD3
LD1
LD4
Indicates
communicating
with MCC
Indicates Thermistor is O/C or
S/C or 43V boost test has failed.
Vigilon 4/6 loops & Compact (VA) panels & network nodes

Write protect link on backplane

The backplane assembly is fitted inside the left side of the backbox.
The backplane has the card slots to facilitate interconnection of plug-in cards, such as the Main
Controller Card (MCC), Loop Processor Cards, IO Cards and Network Cards.
Backplane
LK1
Protected
- write protected
Unprotected
- not write protected
(factory setting)
The backplane also has the flash memory
(NVM) which is under the control of MCC and
is a shared memory to which the system
configuration data is saved.
The link header on the backplane marked
LK1 provides 'write' protection and will stop
the SAVE and BACKUP commands from the
panel controls modifying the memory.
Once the system is fully commissioned the
link LK1 should be configured to 'write
protected', this is important on sites where
customers require compliance to the EN54
Part 2 standard.
The NVM should always hold the complete
system back up.
31