Zones; Groups - Honeywell Vigilon 4 loop Generic Commissioning Instructions

Fire panels & network nodes
Table of Contents

Advertisement

Commissioning instructions

Zones

LOOP1
OHS
Test/Eng
DEVICES
H
ASSIGNED TO
ZONE 4
MCP
INTERFACE
DEVICES
ASSIGNED TO
OHS
ZONE 4
DISABLE
H
MCP
ZONE E
INTERFACE
LOOP2
¨
A Zone has a collection of trigger devices that are located in the same general area. It may be used for one or all of
the following:
for illumination of zonal fire lights on Main panel or Zonal panel or Mimic panel
are also used for common disablement purposes.
¨
There can be up to 128 Zones per A3 or on A2 zonal mimic panel / 64 Zones per A4 zonal mimic panel, the latter
two panel are legacy products
¨
Zones are used to provide local indication of fire at the main panel and to send fire messages to Zonal mimic
panel, Loop Repeat panels and Repeat indicator panels off main panel.
integral zonal indicators on a main panel can be configured to give steady / flashing indication of 1st zone in
fire.
¨
Devices from any loop may be assigned to the same Zone
¨
A device may only be assigned to one Zone
¨
Input/output lines of an interface can not be assigned individually to Zones. The interface lines can only be
assigned collectively to a Zone.
150
ZONE INDICATORS ON THE PANEL (EN system only)
On
1
2
3
4
5
Off
Zones
17
18
19
20
21
Flashing
ZONAL MIMIC PANEL
ZONE 4
ZONE E
NOTE: A DEVICE CAN ONLY BE ASSIGNED TO ONE ZONE
ENABLE
6
7
8
9
10
11
12
13
14
15
16
22
23
24
25
26
27
28
29
30
30
32
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 128

Groups

¨
There can be up to 128 Groups
¨
all devices default to Group 1
¨
all local controller events are in Group 0, ie faults,
warning, silence alarms and reset.
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.