ZX Fire Alarm Control Panels
13 Networks Option
•
Network options define the way in which the panel is configured to operate on a networked system.
These options, such as the panel address, should be checked when a system is first installed, but will
rarely need changing after this time.
•
The network can operate as either a 'Shared Zone' or 'Report and Control' network. A summary of the
network options for various network configurations is given below. Refer to the Network Interface
Guide (P/N 996-075) for detailed information.
•
Press '3' to select the 'Network' option from page 3 of the Commission menus.
•
To change a setting, press either CHANGE or 'No' and then enter the desired setting. Move on using
the 'Yes' key.
13.1 Panel Networks
13.1.1 Network - Panel Network Address
•
The Network Address will have been set to '1' when the panel leaves the factory. If the panel is to be
installed as part of a networked system the address may need to be changed – each panel must have
a unique network address in the range 1 to 99. If the panel is not required on a network, then this
address must be left at '1'.
•
Each panel should be given a unique panel address number.
---------------------------------------------
Panel Network-address number
13.1.2 Standard Network Settings for Shared Zones
•
The following tables give typical settings for a 'shared zone' mini-network system.
Network Option
Panel network-address number
Quantity of slave processors
Use modem
Share zones
Peer-to-Peer
Port B Protocol *
System events
* Port B is not available on ZX1Se or ZX2Se panels.
Commissioning Manual
[ Panel in Commissioning mode ]
Option setting
1 to 99
0
[TRUE]/[FALSE]
[TRUE]/[FALSE]
[TRUE]/[FALSE]
0
[GLOBAL]/[LOCAL]
Table 12 – Slave Panel Network Settings
Document No. 996-175-000-1, Revision 01
=
1 ?
Comments
Enter slave panel address, i.e. 3.
Number of slaves connected to port C.
(DO NOT CHANGE).
Set to TRUE if a modem is connected to port C.
Zones are shared between panels
Pass MUTE / ACCEPT, SILENCE / RESOUND and RESET
key presses back to master.
Use default of 0 unless special application interface
Global -
1.
Passes system events over network
2.
Accepts other network events.
Local -
1.
Does not pass events over the network.
2.
Ignores other network events.
NOTE: The zoned fire status is passed over a shared-zone
network regardless of events being global or local.
MORLEY-IAS
Page 49