Networks Option; Panel Networks; Network - Panel Network Address; Standard Network Settings For Shared Zones - Honeywell Morley-IAS ZX Series Commissioning Manual

Fire alarm control panels
Table of Contents

Advertisement

ZX Fire Alarm Control Panels

13 Networks Option

Network options define the way in which the panel is configured to operate on a networked system.
These options, such as the panel address, should be checked when a system is first installed, but will
rarely need changing after this time.
The network can operate as either a 'Shared Zone' or 'Report and Control' network. A summary of the
network options for various network configurations is given below. Refer to the Network Interface
Guide (P/N 996-075) for detailed information.
Press '3' to select the 'Network' option from page 3 of the Commission menus.
To change a setting, press either CHANGE or 'No' and then enter the desired setting. Move on using
the 'Yes' key.

13.1 Panel Networks

13.1.1 Network - Panel Network Address

The Network Address will have been set to '1' when the panel leaves the factory. If the panel is to be
installed as part of a networked system the address may need to be changed – each panel must have
a unique network address in the range 1 to 99. If the panel is not required on a network, then this
address must be left at '1'.
Each panel should be given a unique panel address number.
---------------------------------------------
Panel Network-address number

13.1.2 Standard Network Settings for Shared Zones

The following tables give typical settings for a 'shared zone' mini-network system.
Network Option
Panel network-address number
Quantity of slave processors
Use modem
Share zones
Peer-to-Peer
Port B Protocol *
System events
* Port B is not available on ZX1Se or ZX2Se panels.
Commissioning Manual
[ Panel in Commissioning mode ]
Option setting
1 to 99
0
[TRUE]/[FALSE]
[TRUE]/[FALSE]
[TRUE]/[FALSE]
0
[GLOBAL]/[LOCAL]
Table 12 – Slave Panel Network Settings
Document No. 996-175-000-1, Revision 01
=
1 ?
Comments
Enter slave panel address, i.e. 3.
Number of slaves connected to port C.
(DO NOT CHANGE).
Set to TRUE if a modem is connected to port C.
Zones are shared between panels
Pass MUTE / ACCEPT, SILENCE / RESOUND and RESET
key presses back to master.
Use default of 0 unless special application interface
Global -
1.
Passes system events over network
2.
Accepts other network events.
Local -
1.
Does not pass events over the network.
2.
Ignores other network events.
NOTE: The zoned fire status is passed over a shared-zone
network regardless of events being global or local.
MORLEY-IAS
Page 49

Advertisement

Table of Contents
loading

Table of Contents