Honeywell Vigilon 4 loop Generic Commissioning Instructions page 123

Fire panels & network nodes
Table of Contents

Advertisement

Message
associated with..
Device
Device Battery OC
number x on loop y
LPC
Device Enabled /
Disabled at Card x
(loop processor card)
ACU
Device Fault number x
on loop y
Audio Control Unit
Beam devices
Device Gain set to x
number y on loop z
(can also be a Flame device -
no longer supported)
Radio (Plexus) Device
Device inoperative
Device
Device Mains Failed /
Restored number x
loop y
Device Mains too high
Devices like: Mimic / Repeat
/ low number x loop y
/ Mains powered interface
unit
Radio (Plexus) Device
Device Moved
Device
Device power Fault /
Restored number x on
loop y
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Vigilon 4/6 loops & Compact (VA) panels & network nodes
meaning..
Failure of fuse or battery wiring is OC on products like
mains powered interface unit.
Normal value = 27.4V
Value is equal to or less than 16V (OC) / greater than
17V (Restored).
Device has been enabled or disabled manually or
automatically.
Fault input has been asserted.
Confirmation of a change in gain setting.
The Radio (Plexus) device batteries are too low for
device to operate correctly
Failure of mains supply to mimic/repeat /mains
powered interface unit. The value of rectified DC is
equal to or less than 8V i.e. failed.
Failure of device mains supply.
The value of rectified DC is too high / low i.e in the
region of 30V / 17V.
The Radio (Plexus) device has been tampered with
The failure of internal power supply rail.
..possible action
Check and replace if necessary to restore.
If necessary manually enable or disable the
device.
Check remote equipment wired to the fault
input.
-
Use the Battery Condition Indicator tool to
determine if the batteries in the Radio (Plexus)
Device require replacing, if necessary replace
the batteries.
Check mains supply connections and the mains
fuse. When the rectified DC is greater than
24V it is restored.
Check the power supply and replace it if
necessary
The Radio (Plexus) device has been moved
from the original installed lobation or there has
been changes in the area that affect the device
operation.
Replace the device.
123