Message
associated with..
Power supply
Loop voltage too
high/low
LPC
Lost Command
number x Loop y
(loop processor card)
Lost Device number x
LPC
on loop y
(loop processor card)
LPC
Lost slave Device
number x on loop y
(loop processor card)
Device
Magnetic switch
operated
number x loop y
Any Card
Main program not
running at
card x
Power supply
Mains failed /
restored
Mains too high
Power supply
Power supply
Mains too low
Power supply
Master alarm
oc
or
sc
Restored
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Vigilon 4/6 loops & Compact (VA) panels & network nodes
meaning..
The ADC value too high.
or
The ADC value is too low.
Lost FAB/SAB.
There is no reply on ends 1&2 of the device.
There is no reply on ends 1&2 of the device.
The reset switch in the base has closed
devices
only.
Problem with software. The watchdog will operate the
MCC / MCB (main control card/board).
Failure is detected when the ADC output from the
rectifier is equal to or less than 105.
The ADC value is too high.
Mains supply is too low.
No end-of-line unit seen.
ADC value is greater than 92
or
ADC value is less than 37
ADC value is 74
..possible action
Check PSU values in the [test/eng] menu,
normal reading is 221. Check fuses and replace
PSU if necessary.
Ignore single occurrence and record in the log
book.
Check the device connections.
Check the slave device connections and replace
if necessary.
for 3400
Check base and proximity of magnetic field.
Software errors will activate a system reset.
Ignore single occurrence.
Record event in the log book.
Check mains and fuse. Replace PSU if
necessary. This should normally equal to 60V to
get a restored message.
Check the PSU values in the [test eng] menu.
Replace PSU if necessary.
Check the wiring to the master alarm circuits.
Ensure EOLs are connected inside the control
panel if master alarm circuits are not used.
129