Commissioning instructions

Fire Routing LEDs (post mid 2015)

Post mid 2015
Sounder
Fire Routing O/P
Active
Fault/Dis
Power
The Fire Alarm Routing Equipment FARE red LED work with FARE Interface
configured to operate as a FARE device. The FARE LEDs illuminate to indicate the
status of FARE.
42

How to configure the LEDs CB253 and CB254 (pre mid 2015)

Pre mid 2015
The switching of the amber LEDs CB253 and CB254 is controlled by
action of command builds 253 and 254 respectively. The switching action
must be configured during commissioning.
Sounder
CB253
Example
This example shows how to configure the panel such that by activating an
CB254
interface input (can be a push button switch on the input), it will cause the
Power
panel LED - CB253 and Master alarms to switch On. If the interface input
switch is released then the panel LED - CB253 and Master alarms will
switch Off.
The following procedures assume a password entry is not required.
# - will appear if a PIN is setup.
Configure the Command build trigger:
Press Menu On/Off button and select [SetUp] -> [Usercode]#, momentarily press <etc> to select [SetUp] ->
[Build] and type in the command build number 253, select [Trigger] -> [IO line] and type in the interface input
channel number, select [Device] and type in the interface device number, select [Loop] and type in the loop
number -> [Enter]. The command build 253 is now configured to be triggered by the interface input.
Configure the Command build label:
Press Menu On/Off button and select [SetUp] -> [Usercode]#, momentarily press <etc> to select [SetUp] ->
[Build] and type in the command build number 253, select [Label] and enter a label of up to 40 characters in
length, select either [Display] to display the label on the panel when the command build 253 is triggered.
Configure the Command build action:
Press Menu On/Off button and select [SetUp] -> [Usercode]#, momentarily press <etc> to select [SetUp] ->
[Build] and type in the command build number 253, select [Action] -> [Start MA] -> [Enter] -> [Reversbl] and
[Enter].
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.