Dip Switch Settings - Honeywell Notifier SFP-2402 Instruction Manual

Table of Contents

Advertisement

DIP Switch Settings

3.1 DIP Switch Settings
The following tables list the programmable features for the SFP-2402 and SFP-2404. Placing a
DIP switch in the ON position will select the feature while placing the DIP switch in the OFF posi-
tion will deselect the feature. The exceptions to this rule are SW3 DIP switches 5 & 6. These two
switches are used to select the Notification Appliance Circuit synchronization feature. A detailed
description of each feature is presented in the following pages.
Important: When any programmable feature is changed by repositioning a DIP switch, the FACP
Reset button must be pressed to ensure that the control panel can read the new switch position.
Switch Number
DIP Switch Number
SW1
SW2
SW3
used to select strobe
synchronization feature as
SFP-2402 & SFP-2404 Series Manual — P/N 51898:F3 8/6/2014
1
Silence Inhibit
2
Auto-silence
3
Temporal Coding
4
Selective Silence (if sync. enabled)
5
Trouble Reminder
6
AC Trouble Delay
7
Autoresettable Supervisory
8
IDC Combination
Waterflow/Supervisory Circuit
1
not used
2
not used
3
IDC1 Verification
4
IDC1 Supervisory
5
IDC2 Verification
6
IDC2 Supervisory
7
not used
8
not used
1
NAC1 Nonsilenceable
2
NAC1 Disable
3
not used
4
not used
No Synchronization
5 & 6
System Sensor Synchronization
shown to the right
Gentex Synchronization
Wheelock Synchronization
7
Nonsilenceable Waterflow for
Combination Circuit
(only if SW1 switch 8 is ON)
8
spare
Table 3.1 SFP-2402 DIP Switch Settings
Program Options via DIP Switch
DIP Switch ON
Switch 5
OFF
ON
OFF
ON
Switch 6
OFF
OFF
ON
ON
31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier sfp-2404Notifier sfp-2402eNotifier sfp-2404e

Table of Contents