Sounders Configuration

¨
The standard alarm devices of each standalone system can be configured for three
sound output signals
¨
every 250mS over a 2 second time the sound output can be altered to high, low or off
tone
¨
sound signal configuration can be altered by modifying the FAB-SAB pairs by
pressing the button Menu On/Off to select [Set-Up] -> <etc-> -> [Modify]-> <etc>
-> [Signal n] -> [Sounder] -> [Enter] and enter the FAB/SAB for Signal n and press
enter.
FABs & SABs
The FAB (first action byte) determines tone and On/Off control while the SAB (second action byte)
determines the action to be performed on the output.
Time in seconds
Factory Default FABs
0
0.25
SABs
Signal 3 (Continuous)
4F
00
Output turns on Low
frequency sound
continuous every 0.5
seconds.
4F
25
Signal 2 (Evacuate)
First output turns on
Low frequency sound
continuously, then every
half second the High
frequency output is
pulsed for 250mS.
65
00
Signal 1 (Alert)
Pulses high frequency
for 250mS every half
second.
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
0.5
0.75
1.0
1.25
1.5
1.75
4F
00
4F
00
4F
00
4F
25
4F
25
4F
25
65
00
65
00
65
00
Vigilon 4/6 loops & Compact (VA) panels & network nodes
Number
FAB action
0
no output
1
-
2
frequency tone
3
-
4
On/Off control.(On being low
frequency)
5
-
6
high frequency tone
7
-
8
-
9
-
A
-
B
-
C
-
D
-
E
F
SAB action
Turns Off selected Outputs
10mS pulse on selected Outputs
40mS pulse on selected Outputs
90mS pulse on selected Outputs
160mS pulse on selected Outputs
250mS pulse on selected Outputs
350mS pulse on selected Outputs
480mS pulse on selected Outputs
630mS pulse on selected Outputs
800mS pulse on selected Outputs
980mS pulse on selected Outputs
1.2S pulse on selected Outputs
1.4S pulse on selected Outputs
1.6S pulse on selected Outputs
1.9S pulse on selected Outputs
Turn on selected Outputs
153