Cards and internal cables of the panel
KEYBOARD INDICATORS AND DISPLAY
WARNING
REMOVAL OF COVER
EXPOSES HIGH VOLTAGE
0V
L2-
L2+
0V
L1-
L1+
PP2
PB1A
PB1B
P2
Network Card
Loop Card 2
Loop Card 1
Battery
The lithium battery
the top connector. The insulation disk must be removed before powering up the system.
BATT3
Remove Sleeve
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Master Control
Board (MCB)
24V
0V
B
A
TX1 RX1 0V
TX2 RX2
L1 0V L2 0V
NC C NO NC C NO NC C NO
L1 0V L2 0V
0V MIPNC C NO
PB15
PB6
PB14
PB10
PB11
PB7
PB9
24V
MA1 - FS1 250mA
FS3 200mA
MA2 - FS2 250mA
P1
CARD 2
P2
CARD 1
FIRMWARE BACKUP
IC3
IC16
SW2
MODE
P16
SW1
RESET
Remove
insulation disk
P13
NVM Protect - [Disabled]
P13
NVM Protect - [Enabled]
s
is disconnected on leaving the factory by means of an insulation disk over
Vigilon 4/6 loops & Compact (VA) panels & network nodes
Set the Rotary switch SW2
This switch is set to the required position for the panel build on leaving the
factory. Before installing the Loop cards and Network card onto the Master
control board MCB ensure the switch
Power Supply Unit
the panel is to be installed in an existing system, see table on the next page.
(PSU)
N E
L
MA1+ MA1- MA2+ MA2-
P2
NVM hardware link P13
PB8
FS3 3.15A(T)
DANGER
Mains fuse
N
L
The NVM can be enabled or disabled by setting the hardware link
MCB. If the NVM protect is hardware disabled then it is also possible to
software enable or disable the NVM using the [Protect] option under the
[Setup] menu at the panel.
Warning
Unprotect: Normally during commissioning the NVM is disabled
Removal of
cover exposes
live parts
DANGER
(unprotected) and writing to NVM is allowed.
Protect: Once the configuration is backed up to the NVM the hardware link
POWER
SUPPLY
P12
must be in the enabled position to disallow writing to the NVM.
P1
P3
P7
BATT3
Installing the Cards
BAT1
FS4
24V
- 1A TE5
FS6
43V
The MCB can accommodate two Loop Cards. One Loop card
FS1
Bat 1
- 3.15A TE5
1A TE5
fitted into the slot labelled CARD1 and the other Loop card
labelled CARD2.
"
SW2
MODE
the slot CARD 2 on the MCB and additionally the Network Card can
accommodate the second Loop card.
SW1
RESET
Earth Link
The earth link lead
must be fitted to the spade connector on the top edge of MCB with the other
end to the spade connector on the Network Card.
Terminals
The terminal blocks
external circuits. The terminal block
for wiring the mains supply to the panel. The connector
bottom edge of the PSU board is used to connect the battery supply.
j
SW2 is set to a required setting if
A networkable system has a Network Card
o
is supplied with the Network Card. This link lead
p
on the top edge of the MCB are used for wiring
q
on the top edge of the PSU is used
r
k
on the
l
can be
n
into the slot
m
fitted into
located on the
35