Honeywell Vigilon 4 loop Generic Commissioning Instructions page 138

Fire panels & network nodes
Table of Contents

Advertisement

Commissioning instructions
Message
associated with..
MCC / MCB
Warning cleared
(main control card/board)
Wiring changed -
LPC
ground break at card
(loop processor card)
x number y on loop z
LPC
Wiring changed -
short at
(loop processor card)
card x number y
loop z
LPC
Wiring changed -
split/closed at
(loop processor card)
card x number y on
loop z
LPC
Wiring changed part
short at card x
(loop processor card)
number y on loop z
Wrong card type at
Any Card
Card x
MCC / MCB
Zone enabled /
(main control card/board)
disabled at
card x
138
meaning..
Warning has been removed.
A test has shown a break on the 0V line. The test is
conducted every minute.
Loop short circuit after the particular device.
No reply received from a device at End-2 of loop.
Less than 80 ohms between the +ve and 0V of loop
wiring.
Card in wrong slot.
The zone has been enabled or disabled automatically or
manually.
..possible action
-
Check wiring of 0V around loop.
Check wiring and device after indicated device.
Check wiring.
Check wiring and the device after the partially
shorted device.
Move the cards to the right location.
If necessary, manually enable or disable the
zone using the [control] menu.
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.