AMT58x-PN ProfiNET®
11.3.1 Setting an isochronous communication
To activate the real-time class 3 both the IO controller and the IO
device must be configured. To do this proceed as follows.
To configure the IO controller (Figure 36) double click the PN-IO slot
X2 to open the PN-IO properties dialog box. The Properties – PN-IO
property sheet will appear. Enter the Synchronization tabbed page
and select the Sync master value in the drop-down menu of the
Synchronization role item; select the High performance value in the
drop-down menu of the IRT option item. Confirm pressing the OK
button.
Figure 36 - Setting the sync master role of the IO controller