5.3.7 Setting the IP address

To help with configuration you are required only once to assign an IP
address. When configuring the PROFINET IO controller in the HW
Config window, STEP 7 opens a dialog for selecting the IP address
and the Ethernet subnetwork.
When the system boots up, the IO controller assigns the IP address
to the IO device. Please make sure that the Assign IP address via IO
controller check box in the Properties dialog box is selected if the IP
address has to be assigned to the encoder via the IO controller.
Anyway the assignment of the IP Address can be disabled by
deselecting the Assign IP address via IO controller check box. In this
case the IP address set in the IO device is used (the IP address is
uploaded from the internal memory). By default, before delivery the
IP address of the encoder is set to 0.0.0.0..
After having set the Device name, you can set the IP Address. To set
the IP address first enter the Properties dialog box by double clicking
the encoder icon in the HW Config window. Check that the Assign IP
address via IO controller check box is selected if you want the IP
address being assigned by the IO controller; otherwise deselect it if
you want it to be uploaded from the internal memory of the IO device.
Press the Ethernet... button in the Node in PROFINET IO system
group if you want to assign an IP address different from the one
suggested by the system. Press the OK button to confirm. Download
data to the PLC pressing the Download button in the Toolbar.

Figure 19 - Setting the IP address