Figure 91 - Firmware Upgrade Operation Process - Datalogic AMT58*-PN Series Instruction Manual

Profinet absolute encoders
Table of Contents

Advertisement

AMT58x-PN ProfiNET®
10.
download progress bars and additional information are shown
in the page during operation;

Figure 91 - Firmware upgrade operation process

11. during download operation S1 Status 1 LED starts blinking
green at 1 Hz while S2 Status 2 LED is OFF (see on page 9);
12. as soon as the operation is carried out successfully, the
FLASH PROGRAMMED SUCCESSFULLY message appears
on the screen;
13.
turn encoder power off and then on to complete the operation.
NOTE
While downloading the firmware upgrading program, unexpected
conditions may arise which could lead to a failure of the installation
process. When such a matter occurs, download process cannot be
carried out successfully and thus the operation is aborted; S2 Status
2 LED starts blinking red at 1 Hz while S1 Status 1 LED is OFF (see
on page 9). In case of flash upgrade error, the program is lost
irreversibly (there is not a bootloader) and the device must be sent
back to Datalogic Automation for restoring.