As explained for the Mode 1, first of all enter the Properties dialog
box by double clicking the encoder icon in the HW Config window
and set the device name in the Device name field. Then press PLC,
Ethernet and then Edit Ethernet node command in the menu bar of
the HW Config window. Press the Browse... button to find all the
nodes connected to the network. Select the IO device you want to
assign the Device name to. The MAC address of the encoder is
written on the encoder label. In the Assign device name group below
in the dialog box, enter the desired name in the Device name field.
Press the Assign Name button to confirm.

Figure 14 - Edit Ethernet Node dialog box

NOTE
The device name default setting is the name from the GSD file. With
integral Profinet interfaces, the device name is derived from the short
description. If several devices of the same type are arranged in the
same Profinet IO system, Step 7 automatically supplements the
name from the GSD file with a serial number. The second device is
assigned the extension "-1", the third device the extension "-2", etc.