OPC UA
#
Anybus error code
0x07
Invalid CmdExt[1]
0x08
Attribute not set-able
0x09
Attribute not get-able
0x0A
Too much data
0x0B
Not enough data
0x0C
Out of range
0x0D
Invalid state
0x0E
Out of resources
0x0F
Segmentation failure
0x10
Segmentation buffer
overflow
0x11
Value too high
0x12
Value to low
0x13
Attribute controlled
0x14
Message channel too small
0x15
General error
0x16
Protected access
0xFF
Object specific
Anybus CompactCom 40 EtherNet/IP IIoT Network Guide
#
OPC UA status code
N/A
N/A
0x803B0000
BadNotWritable
0x803A0000
BadNotReadable
0x80740000
BadTypeMismatch
0x80740000
BadTypeMismatch
0x803C0000
BadOutOfRange
0x80AF0000
BadInvalidState
0x80030000
BadOutOfMemory
0x80020000
BadInternalError
0x80020000
BadInternalError
0x803C0000
BadOutOfRange
0x803C0000
BadOutOfRange
0x801F0000
BadUserAccessDenied
0x80020000
BadInternalError
0x80010000
BadUnexpectedError
0x801F0000
BadUserAccessDenied
N/A
N/A
86 (244)
Comment
Not possible to define a
generic translation. Depends
on what CmdExt[1] contains.
Not possible to define a
generic translation. Depends
on what Anybus object that
is accessed.
SCM-1202–069 1.9 en-US
Need help?
Do you have a question about the CompactCom 40 and is the answer not in the manual?
Questions and answers