Connecting
6.5 Wiring rules
Safety notice for connecting with a LAN ID (Local Area Network)
A LAN or LAN segment with all the interconnected devices should be contained completely in
a single low voltage power distribution in a building. The LAN is designed either for
"Environment A" according to IEEE802.3 or "Environment 0" according to IEC TR 62102.
Do not connect any electrical connectors directly to the telephone network (telephone network
voltage) or a WAN (Wide Area Network).
Note
Protective ground
A PELV circuit contains a connection to protective ground. Without a connection to protective
ground, or in case there is a fault in the connection to the protective ground, the voltage for the
circuit is not stabilized.
Note
Minimum temperature rating of the cable to be connected to the field wiring terminals, 90 °C.
6.5

Wiring rules

When wiring use copper cables with the following AWG* categories or cross-sections.
Wiring rules for ...
connectable cable cross sec‐
tions for flexible cables ...
Stripped length of the cable
Wire end ferrule according to DIN 46228 without plastic ferrule**
* AWG: American Wire Gauge
** See note "Wire end ferrules"
Note
Wire end ferrules
Use crimp shapes with smooth surfaces, such as provided by square and trapeze shaped crimp
cross sections.
Crimp shapes with wave-shaped profile are unsuitable.
46
WARNING
without wire end ferrule
with wire end ferrule with plastic
ferrule**
with TWIN wire end ferrule without
plastic ferrule**
Equipment Manual, 12/2023, C79000-G8976-C659-03
Spring-loaded terminals
0.2 - 1.5 mm
2
AWG: 24 - 16
0.25 - 0.75 mm
2
AWG: 24 - 18
0.25 - 1.5 mm
2
AWG: 24 - 16
10 mm
10 mm