Releasing Applications
Each Cross Zone option and the conditions required to activate releasing zone ZR01 are shown in
the table below, according to the example in Figure B.8.
Cross Zone
Selection (Cross=)
Cross=No
Cross=Yes
Cross=Zone
For example:
Cross=Heat
B.3.6 Using Type Codes for Releasing Zones
The control panel provides a set of Type Codes designed for releasing applications for inputs and
outputs. This section details how to program each of these Type Codes.
Type Codes designed for releasing zone inputs (SLC monitor modules).
Type Code
ABORT SWITCH
(tracking)
.
MAN
RELEASE
(latching)
MAN REL DELAY
(latching)
SECOND SHOT
(latching)
Type Codes designed for releasing zone outputs (SLC control modules).
Type Code
REL END BELL
REL CKT ULC
RELEASE CKT
.
REL
FORM C
REL AUDIBLE
INST RELEASE
94
Condition(s) Required to Activate the Releasing zone
An alarm from any initiating device activates the releasing zone.
An alarm from any two initiating devices activates the releasing zone.
An alarm from two initiating devices mapped to different primary general zones, but
mapped to the same releasing zone.
• An alarm from L02D101 and L02D103
• An alarm from L02D102 and L02D104
• An alarm from L02D101 and L02D104
• An alarm from L02D102 and L02D103
The two detectors listed in each set above are each mapped to different primary
general zones, but both list ZR01 in their zone maps.
Activation of heat detector L02D104 and one smoke detector (L02D101, L02D102,
or L02D103).
What the Type Code does
Provides an abort function through a
monitor module (connected to a UL-listed
abort station) for a releasing zone.
Provides a manual release through a
monitor module (connected to a UL-listed
pull station) for a releasing zone.
Provides a manual release with a
10-second delay through a monitor
module (connected to a UL-listed pull
station) for a releasing zone.
Provides a second manual release
through a monitor module (connected to a
UL-listed pull station) for a releasing zone.
What the Type Code does
Activates an NAC audio or visual device
when releasing circuits shut off.
Directs outputs to perform a release
function as required by ULC.
Directs outputs to perform a releasing
function.
Directs relay outputs to perform a
releasing function.
Activates audio or visual devices steady
when releasing starts.
Activates non-releasing output (SLC
modules) with no delay time.
NFS2-3030 Programming Manual — P/N 52545:A 11/29/2005
Abort Switches
Refer to
"How to Program an Abort Switch" on
page 95
"How to Program a Manual Release
Switch" on page 96
"How to Program a Manual Release
Delay Switch" on page 97
"How to Program a Second Shot Switch"
on page 98
Refer to
"How to Program a Release End Bell
Circuit" on page 99
"How to Program a ULC Release Circuit"
on page 100
"How to Program a Release Circuit" on
page 101
"How to Program a Release Form-C
Circuit" on page 102
"How to Program a Release Audible
Circuit" on page 103
"How to Program an Instant Release
Circuit" on page 104