Central Station Account
CELLULAR OPTIONS
1=ENABLED
2=CS ACCOUNT
Cellular Options Screen #1
Enter the City ID, Central Station ID, and Account Code all provided by the monitoring station.
Supervision Settings
ETHERNET OPTIONS
1=SUPV. SETTINGS
NFPA 2010 DUAL PATH
Ethernet Options Screen #2
• NFPA 2010 Dual Path: Supervision Interval: 24 Hours
• NFPA 2010 Sole Path: Supervision Interval: 5 min
• NFPA 2013 Dual Path: Supervision Interval: 6 Hours
• NFPA 2013 Sole Path: Supervision Interval: 1 Hour
NOTE: These supervision settings apply to both the Cellular settings and the Ethernet settings.

Trouble Report Limit (Dialer Runaway Prevention)

COMMUNICATOR
1=PRI COMM PATH
2=SEC COMM PATH
3=TBL REPORT LIMIT
Communicator Screen #2
To set the Trouble Report Limit, press 3 while viewing Communicator Screen #1. The following screen will be displayed.
Enter a value between 00 and 99, then press Enter to set the Report Limit to this value. Refer to the table on page 47 for permissible settings.
NOTE: Entering a value of 00 will disable the Trouble Report Limit allowing the Communicator to call the Central Station an unlimited number
of times.

Report Style

COMMUNICATOR
1=REPORT STYLE

2=EVENT CODES

Communicator Screen #3
NOTE:
1. Detector Address 001 will be reported to the Central Station as Point 001, Detector Address 002 as Point 002, with reports continuing in a
similar fashion all the way up to Detector Address 50 which will be reported as Point 050.
2. Module Address 001 will be reported to the Central Station as Point 160, Module Address 002 will be reported to the Central Station as Point
161, with reports continuing in a similar fashion all the way up to Module Address 50 which will be reported as Point 209.
Event Codes
COMMUNICATOR
1=REPORT STYLE
2=EVENT CODES
Communicator Screen #3
84
Press 2 on Cellular Options Screen #1 to display the following:
NO
Pressing 1 while viewing Ethernet Options Screen #2 will cause the display to toggle between the 4 supervi-
sion setting options. Toggle to select NFPA 2010 Sole Path, NFPA 2010 Dual Path, NFPA 2013 Sole Path, or
NFPA 2013 Dual Path. Refer to the table on page 47 for permissible settings.
The Supervision Interval is the time from the check-in at AlarmNet to the FACP. Select Dual Path when Ether-
net and Cellular communications will be used. Select Sole Path when only Ethernet or Cellular is used.
The Report Limit option limits the number of Communicator trouble calls to the Central Station, to a pro-
grammed amount between 0 and 99, for each unique trouble within a 24 hour period. Separate limit counters
keep track of each unique type of trouble. Note that the number of phone line (communication) faults called to
0
the Central Station are not limited by this feature. No subsequent restoral message is sent to the Central Sta-
tion(s) for a particular trouble whose call limit has been reached. Local communicator annunciation will still
track the particular trouble and restoral.
Pressing 1 while viewing Communicator Screen #3 will cause the Report Style display to toggle between Point
and Zone. Setting the Report Style to Point will program the Communicator to report individual point status to
POINT
the Central Station. The control panel is capable of monitoring a total of 50 addressable devices. Setting the
Report Style to Zone will program the Communicator to report zone status to the Central Station. The control
panel is capable of monitoring a total of 20 individual zones.
Pressing 2 while viewing the Communicator Screen #3 will cause the following screen to be displayed:
POINT
CS ACCOUNT
1=CITY ID
0000
2=CS ID
0000
3=ACCT CODE
000000
Central Station Account Screen
TROUBLE CALL LIMIT
RANGE 00-99
Trouble Report Limit Screen
EVENT CODES
1=ADEMCO CONTACT ID
2=SIA8
3=SIA20
Event Code Screen
ES-50X Series Manual — P/N LS10129-000FL-E:D 4/26/2021