Master Programming Level
To set the Trouble Report Limit, press 3 while viewing Communicator Screen #1. The following screen will be displayed.
Enter a value between 00 and 99, then press Enter to set the Report Limit to this value. Refer to the table on page 49 for permissible set-
tings.
NOTE: Entering a value of 00 will disable the Trouble Report Limit allowing the Communicator to call the Central Station an unlimited
number of times.

Report Style

COMMUNICATOR
1=REPORT STYLE POINT

2=EVENT CODES

Communicator Screen #3
NOTE:
1. Detector Address 001 will be reported to the Central Station as Point 001, Detector Address 002 as Point 002, with reports continuing in
a similar fashion all the way up to Detector Address 99 which will be reported as Point 099.
2. Module Address 001 will be reported to the Central Station as Point 160, Module Address 002 will be reported to the Central Station as
Point 161, with reports continuing in a similar fashion all the way up to Module Address 99 which will be reported as Point 258.
Event Codes
COMMUNICATOR
1=REPORT STYLE POINT
2=EVENT CODES
Communicator Screen #3
Select the desired communication format to update Event Code programming.
Pressing the down arrow key allows viewing of all Events associated with the selected Communication Format. Pressing the number cor-
responding to the event displayed in each screen will display its default event code which can be customized by the programmer. For
example, pressing 1 for Pull Station will display the following screen which allows the Event Code to be changed from the default value.
The tables on the following pages list all of the Events and their default Event Codes for the various Communication Formats.
The information shown in Table 3.3 is automatically programmed for the Central Station phone number Event Codes when the Ademco
Contact ID or SIA Format is selected. Enter 0s for an Event Code Setting to disable the report. Disabled reports will not get called to the
Central Station. The programmer may enable the Event Types in programming as described on the previous page.
Event Description
PULL STATION
MON-USER-DEF-1
WATERFLOW
MON-USER-DEF-2
SMOKE (PHOTO)
DET-USER-DEF-1
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
TROUBLE CALL LIMIT
00-99 RANGE

Trouble Report Limit Screen
Pressing 1 while viewing Communicator Screen #3 will cause the Report Style display to toggle between
Point and Zone. Setting the Report Style to Point will program the Communicator to report individual point
status to the Central Station. The control panel is capable of monitoring a total of 198 addressable devices.
Setting the Report Style to Zone will program the Communicator to report zone status to the Central Sta-
tion. The control panel is capable of monitoring a total of 99 individual zones.
Pressing 2 while viewing the Communicator Screen #3 will cause the following screen to be displayed:
EVENT CODES
1=ADEMCO CONTACT ID
2=SIA 8
3=SIA 20
Event Code Screen
EVENT CODES
1=PULL STATION
2=MON-USER-DEF-1
3=WATERFLOW
Event Code Screen
PULL STATION
ALARM
Event Code Screen
Ademco Contact ID
Active
115
115
113
113
111
111
Table 3.3 Event Codes
000
Zone
Point
Zone
Point
Zone
Point
Zone
Point
Zone
Point
Zone
Point
Zone
Point
Programming
SIA
Active
Restoral
FA
FH
FA
FH
SA
SH
SA
SH
FA
FH
FA
FH
87