Configure fieldbus
7.2 Communication via PROFINET
7.2.3

Configuring communication to the control

Configuring the communication using SIMATIC S7 control
You have the following options, if the inverter is not included in the hardware library:
● Install the most up to date STARTER version
● Install the GSDML of the inverter using "Tools/Install GSDML file" in HW Config.
Additional information on this topic is provided in the "Fieldbuses" Function Manual, also see
Manuals for your converter (Page 334).
Configuring the communication using a non-Siemens control
1. Import the device file (GSDML) of the inverter into the engineering tool for your control
system.
2. Configure the communication.
7.2.4

Select telegram

Precondition
In the basic commissioning, you have selected a setting with fieldbus.
See also Section: Basic commissioning (Page 84).
Procedure
Proceed as follows to set a specific telegram in the inverter:
Using STARTER or an operator panel, set parameter p0922 to the appropriate value.
You have set a specific telegram in the inverter.
The following telegrams are available:
Parameter
p0015
p0922
128
Description
Macro drive unit
Configure the interface in basic commissioning, and select a telegram.
PROFIdrive Telegram selection
Set the send and receive telegram, also see Cyclic communication (Page 133)
1:
Standard telegram 1, PZD-2/2 (factory setting)
20:
Standard telegram 20, PZD-2/6
350:
SIEMENS telegram 350, PZD-4/4
352
SIEMENS telegram 352, PZD-6/6
353:
SIEMENS telegram 353, PZD-2/2, PKW-4/4
354:
SIEMENS telegram 354, PZD-6/6, PKW-4/4
999:
Extend telegrams and change signal interconnection (Page 139)
SINAMICS G110M Operating Instructions
Operating Instructions, 04/2015, FW V4.7.3, A5E31298649B AD