6.1 Configure Response Time

Menu > Configuration > Process Measurement > Response Time
Display
Device Tools > Configuration > Process Measurement > Response Time
ProLink III
Configuration > Process Measurement > Response Time
Web browser
Response Time controls the speed of various internal processes that are involved in retrieving electronic data
from the sensor and converting it to process data.
Response Time affects all process and diagnostic variables.
Restriction
Response Time is configurable only if you are using the enhanced core processor. If you are using the
standard core processor, Response Time is set to Low Filtering and cannot be changed.
Procedure
Set Response Time as desired.
Option
Description
Normal
Appropriate for typical applications.
High Filtering Slower response. Appropriate for applications with significant amount of entrained gas or
process noise.
Low Filtering Fastest response. Appropriate for proving or filling applications.
Service
Do not select unless directed by Micro Motion personnel.

6.2 Detect and report two-phase flow

Two-phase flow (gas in a liquid process or liquid in a gas process) can cause a variety of process control issues.
The transmitter provides two methods to detect and report or respond to two-phase flow.
6.2.1 Detect two-phase flow using density
Display
Menu > Configuration > Process Measurement > Density
ProLink III
Device Tools > Configuration > Process Measurement > Density
Web browser
Configuration > Process Measurement > Density
Configuration and Use Manual

Configure advanced options for process measurement

March 2019
83

Advertisement

Table of Contents
loading

Table of Contents