Integrate the meter with the control system
March 2019
Table 8-2: Interaction between actual flow direction and Sensor Flow Direction Arrow
Actual flow direction
Reverse (opposite from Flow arrow on
sensor)
Procedure
Set Frequency Output Direction as desired.
Option
Description
Positive Flow Only
Negative Flow
Only
Both Positive and
The Frequency Output reports the absolute value of the flow rate according to the
Negative Flow
configured scaling method. It is not possible to distinguish between forward flow and
reverse flow from the Frequency Output alone. This setting is typically used in
combination with a discrete output configured to report flow direction.
Related information
Configure Sensor Flow Direction Arrow
Configure Discrete Output Source
8.5.4 Configure Frequency Output Fault Action
Menu > Configuration > Inputs/Outputs > Channel C > I/O Settings > Fault Action
Display
ProLink III
Device Tools > Configuration > I/O > Outputs > Frequency Output x > Fault Action
Web browser
Configuration > Inputs/Outputs > Channel C > Frequency Output > Fault Action
Frequency Output Fault Action controls the behavior of the Frequency Output if the transmitter detects a
fault condition.
Important
The fault action is implemented only if Alert Severity is set to Failure. If Alert Severity is set to any other
option, the fault action is not implemented.
For some faults only: If Fault Timeout is set to a non-zero value, the transmitter will not implement the
fault action until the timeout has elapsed.
Procedure
1. Set Frequency Output Fault Action as desired.
122
Setting of Sensor Flow Direction
Arrow
With Arrow
Against Arrow
Forward flow: The Frequency Output reports the flow rate according to the
configured scaling method.
Reverse flow: The Frequency Output is 0 Hz.
Forward flow: The Frequency Output is 0 Hz.
Reverse flow: The Frequency Output reports the absolute value of the flow rate
according to the configured scaling method.
Configuration and Use Manual
Flow direction sent to outputs and
totalizers
Reverse
Forward
Micro Motion Model 5700 with Ethernet Transmitters
MMI-20029769