Configure process measurement applications
March 2019
Example
The current measurement unit for mass flow rate is g/sec. The batch will be configured and measured
in g (grams).
3. Set Max Target to the largest batch that will be allowed.
Default: 999999999.0 kg or the equivalent value in the configured measurement unit
Range: Unlimited
If you try to set the batch target to a larger amount, the transmitter will reject the setting.
4. Set Max Batch Time to the maximum number of seconds that a batch will be allowed to run.
If the batch does not reach its target before this period expires, the batch is halted automatically and
an alert is posted.
Default: 0 seconds
Range: 0 to 86,400 seconds (1 day)
If Maximum Fill Time is set to 0, the control is disabled and no maximum time is applied to batches.
5. (Optional) For two-stage batching, set the following parameters:
Two-stage batching is a batch that is run on a gas and liquid mixture flowing through a pipeline.
Parameter
Number of Stages
Configure Presets by
6. Optional: To enable Reset on Start, select Yes.
Option
Enabled (Yes)
Disabled (No)
The default setting of Reset on Start is Enabled. If the custody transfer application is installed, Reset on
Start is set to No and cannot be changed.
74
Value
Set to 2.
Setting this parameter to 1 disables two-stage batching.
% Target
Quantity
Description
The batch totalizer resets when the operator starts the batch.
The operator must press RESET before starting a new batch.
Configuration and Use Manual
The values for Open Primary, Open Secondary, Close
Primary, and End Warning are each configured as a
percent of target.
The values for Open Primary and Open Secondary are
each configured as a quantity at which the valve should
open. The values for Close Primary and End Warning
are each configured as a quantity that is subtracted
from the target.
Micro Motion Model 5700 with Ethernet Transmitters
MMI-20029769