Electrical Wiring - Control Cables; Overview - Danfoss VLT AutomationDrive FC 360 Programming Manual

Hide thumbs Also See for VLT AutomationDrive FC 360:
Table of Contents

Advertisement

Introduction
1
1

1.3 Electrical Wiring - Control Cables

1.3.1 Overview

+10 V DC
0-10 V DC
0/4-20 mA
0-10 V DC
0/4-20 mA
Illustration 1.3 Basic Wiring Schematic Drawing
A=Analog, D=Digital
1) Built-in brake chopper available from 0.37-22 kW
2) Relay 2 is 2-pole for J1-J3 and 3-pole for J4-J7. Relay 2 of J4-J7 with terminal 4,5,6, same NO/NC logic as Relay 1. Relays
are pluggable in J1-J5, and fixed in J6-J7.
3) Dual DC choke in 30-75 kW (J6 & J7)
4) Switch S801 (bus terminal) can be used to enable termination on the RS-485 port (terminals 68 and 69)
5) No BR for 30-75 kW (J6 & J7)
10
RFI
91 (L1)
3 Phase
92 (L2)
power
93 (L3)
input
95
PE
50 (+10 V OUT)
53 (A IN)
54 (A IN)
55 (COM A IN)
12 (+24 V OU T)
18 (D IN)
19 (D IN)
20
(COM D IN)
27
(D IN/OUT)
29
(D IN/OUT)
32 (D IN)
33 (D IN)
31 (D IN)
Danfoss A/S © Rev. 2014-03-31 All rights reserved.
Programming Guide
3)
Switch Mode
Power Supply
10 V DC
24 V DC
15 mA
100 mA
+
-
+
-
P 5-00
24 V (NPN)
0 V (PNP)
24 V (NPN)
0 V (PNP)
24 V (NPN)
4)
0 V (PNP)
24 V
0 V
5V
24 V (NPN)
0 V (PNP)
24 V
0 V
RS-485
Interface
24 V (NPN)
0 V (PNP)
24 V (NPN)
0 V
0 V (PNP)
24 V (NPN)
0 V (PNP)
(U) 96
(V) 97
(W) 98
(PE) 99
(-UDC) 88
1)
Brake
(+UDC) 89
resistor
(BR) 81
5)
Relay 1
03
240 V AC, 2 A
02
01
Relay 2 2)
06
240 V AC, 2 A
05
04
(A OUT) 45
Analog Output
0/4-20 mA
(A OUT) 42
ON=Terminated
OFF=Open
S801
0V
RS-485
(N RS-485)
69
(P RS-485)
68
(COM RS-485) 61
(PNP) = Source
(NPN) = Sink
Motor
MG06C402

Advertisement

Table of Contents
loading