Danfoss VLT AutomationDrive FC 360 Programming Manual page 39

Hide thumbs Also See for VLT AutomationDrive FC 360:
Table of Contents

Advertisement

Parameter Descriptions
1-93 Thermistor Source
Option:
Function:
NOTICE
This parameter cannot be changed
while the motor is running.
NOTICE
Digital input should be set to [0] PNP -
Active at 24 V in 5-00 Digital I/O Mode.
Select the input to which the thermistor
(PTC sensor) should be connected. An
analog input option [1] Analog Input 53 or
[2] Analog Input 54 cannot be selected if the
analog input is already in use as a reference
source (selected in parameter 3-15 Reference
1 Source, parameter 3-16 Reference 2 Source
or parameter 3-17 Reference 3 Source.
[0]
None
*
[1]
Analog Input
53
[2]
Analog Input
54
[3]
Digital input
18
[4]
Digital input
19
[5]
Digital input
32
[6]
Digital input
33
[7]
Digital input
31
MG06C402
Programming Guide
Danfoss A/S © Rev. 2014-03-31 All rights reserved.
4
4
37