Danfoss VLT AutomationDrive FC 360 Programming Manual page 79

Hide thumbs Also See for VLT AutomationDrive FC 360:
Table of Contents

Advertisement

Parameter Descriptions
9-63 Actual Baud Rate
Option:
Function:
[7]
3000 kbit/s
[8]
6000 kbit/s
[9]
12000 kbit/s
[10]
31,25 kbit/s
[11]
45,45 kbit/s
[255]
No baudrate found
*
9-64 Device Identification
Range:
Function:
0
[0 -
The device identification parameter. The data type
*
0 ]
is "Array[n] of Unsigned16". The assignment of the
first subindexes is defined and shown in Table 4.7.
NOTICE
This parameter is not visible via LCP.
Index
Content
0
Manufacturer
1
Device type
2
Version
3
Firmware date year yyyy
4
Firmware date
month
5
No. of axes
6
Vendor specific: PB
Version
7
Vendor specific:
Database Version
8
Vendor specific:
AOC Version
9
Vendor specific:
MOC Version
9-65 Profile Number
Range:
Function:
0
[0 - 0 ] This parameter contains the profile identification.
*
Byte 1 contains the profile number and byte 2 the
version number of the profile.
NOTICE
This parameter is not visible via LCP.
9-67 Control Word 1
Range:
0
[0 - 65535 ]
*
9-68 Status Word 1
Range:
0
[0 - 65535 ]
*
MG06C402
Programming Guide
9-70 Edit Set-up
Option:
[1]
[2]
[9]
9-71 Profibus Save Data Values
Option:
Value
128
1
xxyy
ddmm
[0]
variable
[1]
xxyy
xxyy
[2]
xxyy
xxyy
9-72 ProfibusDriveReset
Option:
[0]
[1]
[2]
[3]
Function:
9-75 DO Identification
Function:
Range:
0
*
Danfoss A/S © Rev. 2014-03-31 All rights reserved.
Function:
Select the set-up in which programming
(change of data) is performing during
operation. It is possible to programme the 4
set-ups independently of the set-up selected as
active. Parameter access from each master is
directed to the set-up which is selected by the
individual master (cyclic, acylic MCL1, first
acyclic MCL2, second acyclic MCL2, third acyclic
MCL2).
Set-up 1
Set-up 2
Active Set-
*
up
Function:
Parameter values changed via Profibus are not
automatically stored in non-volatile memory. Use
this parameter to activate a function that stores
parameter values in the EEPROM non-volatile
memory, so changed parameter values are
retained at power-down.
Off
Deactivates the non-volatile storage function.
*
Store all
Stores all parameter values in the set-up selected
setups
in parameter 9-70 Edit Set-up in the non-volatile
memory. The selection returns to [0] Off when all
values have been stored.
Store all
Stores all parameter values for all set-ups in the
setups
non-volatile memory. The selection returns to [0]
Off when all parameter values have been stored.
Function:
No action
*
Power-on reset
Resets frequency converter upon power-
up, as for power-cycle.
Power-on reset
prep
Comm option
When reset, the frequency converter
reset
disappears from the fieldbus, which may
cause a communication error from the
master.
NOTICE
Resets the Profibus option only.
[0 - 65535 ]
4
Function:
77
4