Parameter Descriptions
6-73 Terminal 45 Output Min Scale
Range:
Function:
0 %
[0 - 200
Scale for the minimum output (0 or 4 mA) of
*
%]
the analog signal at terminal 45. Set the value
to be the percentage of the full range of the
variable selected in parameter 6-71 Terminal 45
Analog Output.
6-74 Terminal 45 Output Max Scale
Range:
Function:
100 %
[0 - 200
Scale for the maximum output (20 mA) of the
*
%]
analog signal at terminal 45. Set the value to
be the percentage of the full range of the
variable selected in parameter 6-71 Terminal
45 Analog Output.
6-76 Terminal 45 Output Bus Control
Range:
Function:
0
[0 - 16384 ] Holds the level of analog output if controlled
*
by bus.
4.7.5 6-9* Analog/Digital Output 42
Parameters for configuring the limits for analog/digital
output Terminal 42. Analog outputs are current outputs:
0/4-20 mA. Resolution on analog outputs is 12 bit. Analog
output terminals can also be set-up as digital output.
6-90 Terminal 42 Mode
Option:
Function:
Set terminal 42 to act as analog output or
as digital output.
[0]
0-20 mA
*
[1]
4-20 mA
[2]
Digital Output
6-91 Terminal 42 Analog Output
Option:
[0]
No operation
*
[100]
Output frequency
[101]
Reference
[102]
Process Feedback
[103]
Motor Current
[104]
Torque rel to limit
[105]
Torq relate to rated
[106]
Power
[107]
Speed
[111]
Speed Feedback
[113]
Ext. Closed Loop 1
[139]
Bus Control
[143]
Ext. CL 1
[162]
Tapered tension set point
[254]
DC Link Voltage
MG06C402
Programming Guide
6-92 Terminal 42 Digital Output
Option:
[0]
*
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]
[14]
[15]
[16]
[17]
[18]
[19]
[20]
[21]
[22]
[23]
[24]
[25]
[26]
[27]
[28]
[29]
[30]
[31]
[32]
[36]
[37]
Function:
[40]
[41]
[42]
[45]
[46]
[47]
[56]
[60]
[61]
[62]
[63]
[64]
[65]
[70]
[71]
[72]
[73]
Danfoss A/S © Rev. 2014-03-31 All rights reserved.
No operation
Control Ready
Drive ready
Drive rdy/rem ctrl
Stand-by / no warning
Running
Running / no warning
Run in range/no warn
Run on ref/no warn
Alarm
Alarm or warning
At torque limit
Out of current range
Below current, low
Above current, high
Out of frequency range
Below frequency, low
Above frequency, high
Out of feedb. range
Below feedback, low
Above feedback, high
Thermal warning
Ready, no thermal warning
Remote,ready,no TW
Ready, no over-/ under voltage
Reverse
Bus OK
Torque limit & stop
Brake, no brake warning
Brake ready, no fault
Brake fault (IGBT)
Relay 123
Mech brake ctrl
Control word bit 11
Control word bit 12
Out of ref range
Below reference, low
Above ref, high
Bus ctrl.
Bus control, timeout: On
Bus control, timeout: Off
Heat sink cleaning warning, high
Comparator 0
Comparator 1
Comparator 2
Comparator 3
Comparator 4
Comparator 5
Logic rule 0
Logic rule 1
Logic rule 2
Logic rule 3
Function:
4
4
63

Advertisement

Table of Contents
loading

Table of Contents