Parameter Descriptions
4 Parameter Descriptions
4.1 Parameters: 0-** Operation and Display
Parameters related to the fundamental functions of the
frequency converter, function of the LCP keys and configu-
ration of the LCP display.
4
4
4.1.1 0-0* Basic Settings
0-01 Language
Option:
[0]
*
[10]
0-03 Regional Settings
Option:
[0]
Interna-
*
tional
[1]
US
0-04 Operating State at Power-up (Hand)
Option:
[0]
Resume
[1]
Forced stop,
*
ref=old
[2]
Forced stop,
ref=0
20
Function:
English
Chinese
Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
Activates 1-20 Motor Power [kW] for setting the
motor power in kW and sets the default value
of 1-23 Motor Frequency to 50 Hz.
Activates 1-20 Motor Power [kW] for setting the
motor power in hp and sets the default value of
1-23 Motor Frequency to 60 Hz.
Function:
Selects the operating mode upon
reconnection of the frequency converter to
mains voltage after power down in Hand
(local) operation mode.
Restarts the frequency converter, maintaining
the same start/stop settings (applied by
[Hand On/Off]) as before the frequency
converter was powered down.
Restarts the frequency converter with a saved
local reference, after mains voltage reappears
and after pressing [Hand On].
Resets the local reference to 0 upon
restarting the frequency converter.
Danfoss A/S © Rev. 2014-03-31 All rights reserved.
Programming Guide
0-06 GridType
Option:
[10]
380-440V/50Hz/IT-
grid
[11]
380-440V/50Hz/
Delta
[12]
380-440V/50Hz
[20]
440-480V/50Hz/IT-
grid
[21]
440-480V/50Hz/
Delta
[22]
440-480V/50Hz
[110] 380-440V/60Hz/IT-
grid
[111] 380-440V/60Hz/
Delta
[112] 380-440V/60Hz
[120] 440-480V/60Hz/IT-
grid
[121] 440-480V/60Hz/
Delta
[122] 440-480V/60Hz
0-07 Auto DC Braking
Option: Function:
[0]
Off Function is not active.
[1]
On
*
Function:
Select the grid type of the supply
voltage/frequency.
NOTICE
Not all choices are supported in
all power sizes.
IT grid is a supply mains, where the
neutral point of secondary side of the
transformer is not connected to
ground.
Delta is a supply mains where the
secondary part of the transformer is
delta-connected and one phase is
connected to ground.
Protective function against overvoltage at coast.
WARNING
Can cause PWM when coasted.
Function is active.