Drive Status; Ref. & Feedb; Inputs And Outputs - Danfoss VLT AutomationDrive FC 360 Programming Manual

Hide thumbs Also See for VLT AutomationDrive FC 360:
Table of Contents

Advertisement

Parameter Descriptions
16-18 Motor Thermal
Range:
0 %
[0 - 100
*
%]
16-22 Torque [%]
4
4
Range:
0 %
[ -200 - 200 % ] View the torque in percent of nominal
*

4.15.3 16-3* Drive Status

16-30 DC Link Voltage
Range:
0 V
[0 - 65535 V] View a measured value. The value is filtered
*
16-33 Brake Energy /2 min
Range:
0 kW
[0 - 10000
*
kW]
16-34 Heatsink Temp.
Range:
0 °C
[-128 - 127
*
°C]
16-35 Inverter Thermal
Range:
0 %
[0 - 255 %]
*
16-36 Inv. Nom. Current
Range:
0 A
[0 - 655.35 A] View the inverter nominal current, which
*
16-37 Inv. Max. Current
Range:
0 A
[0 - 655.35 A] View the inverter maximum current, which
*
98
Programming Guide
Function:
View the calculated thermal load on the motor.
The cut-out limit is 100%. The basis for
calculation is the ETR function selected in
parameter 1-90 Motor Thermal Protection.
Function:
torque, with sign, applied to the motor
shaft.
Function:
with a 30 ms time constant.
Function:
View the brake power transmitted to an
external brake resistor. The mean power
is calculated on an average basis for the
most recent 120 s.
Function:
View the frequency converter heat sink
temperature. The cut-out limit is 90 ±5 °C,
and the motor cuts back in at 60 ±5 °C.
Function:
View the percentage load on the inverter.
Function:
should match the nameplate data on the
connected motor. The data are used for
calculation of torque, motor protection, etc.
Function:
should match the nameplate data on the
connected motor. The data are used for
calculation of torque, motor protection, etc.
Danfoss A/S © Rev. 2014-03-31 All rights reserved.
16-38 SL Controller State
Range:
Function:
0
[0 - 20 ] View the state of the event under execution by
*
the SL controller.
16-39 Control Card Temp.
Range:
Function:
0 °C
[0 - 65535 °C] View the temperature on the control card,
*
stated in °C.
4.15.4 16-5* Ref. & Feedb.
16-50 External Reference
Range:
Function:
0 %
[-200 - 200
View the total reference, the sum of
*
%]
digital, analog, preset, bus and freeze
references, plus catch-up and slow-down.
16-52 Feedback[Unit]
Range:
0
[-4999 - 4999
ProcessCtrlUnit
ProcessCtrlUnit]
*
16-53 Digi Pot Reference
Range:
0
[-200 - 200 ]
*
16-57 Feedback [RPM]
Range:
Function:
0 RPM
[-30000 -
Readout parameter where the actual motor
*
30000 RPM]
RPM from the feedback source can be read
in both closed loop and open loop. The
feedback source is selected by
parameter 7-00 Speed PID Feedback Source.

4.15.5 16-6* Inputs and Outputs

16-60 Digital Input
Range:
Function:
0
[0 -
View the actual state of the digital inputs 18,
*
65535 ]
19, 27 and 29.
Function:
View the feedback unit
resulting from the selection
of unit and scaling in
parameter 3-00 Reference
Range,
parameter 3-01 Reference/
Feedback Unit,
parameter 3-02 Minimum
Reference and
parameter 3-03 Maximum
Reference.
Function:
MG06C402