Parameter Descriptions
6-63 Terminal X30/8 Bus Control
Range:
0.00 %
[0.00 - 100.00 %] Holds the level of Output X30/8 if
*
3
3
6-64 Terminal X30/8 Output Timeout Preset
Range:
0.00 %
[0.00 - 100.00
*
%]
3.8.8 6-7* Analog Output 3 MCB 113
Parameters for configuring the scaling and limits for analog
output 3, Terminal X45/1 and X45/2. Analog outputs are
current outputs: 0/4 – 20mA. Resolution on analog output is
11 bit.
6-70 Terminal X45/1 Output
Option:
[0]
No
operation
[52]
MCO 305
0-20mA
[53]
MCO 305
4-20mA
[100] Output
frequency
0-20mA
[101] Reference
0-20mA
[102] Feedback
[103] Motor
current
0-20mA
[104] Torque rel
to lim
0-20mA
[105] Torque rel
to rated
94
FC 300 Programming Guide
Function:
controlled by bus.
Function:
Holds the preset level of Output X30/8.
In case of a bus timeout and a timeout
function is selected in 6-60 Terminal
X30/8 Output, the output will preset to
this level.
Function:
Select the function of Terminal X45/1 as an
analog current output.
When no signal on the analog output.
0hz = 0mA; 100hz = 20mA.
3-00 Reference Range [Min - Max] 0% = 0mA;
100% = 20mA
3-00 Reference Range [-Max - Max] -100% =
0mA; 0% = 10mA; +100% = 20mA
Value is taken from 16-37 Inv. Max. Current.
Inverter max. current (160% current) is equal
to 20mA.
Example: Inverter norm current (11kW) = 24 A.
160% = 38.4 A. Motor norm current = 22 A
Read-out 11.46mA.
mA x 22 A
20
mA
= 11.46
A
38.4
In case the norm motor current is equal to
20mA, the output setting of 6-52 Terminal 42
Output Max Scale is:
I VLT
x 100
Max
x 100
38.4
=
= 175 %
I Motor
22
Norm
The torque setting is related to setting in
4-16 Torque Limit Motor Mode
The torque is related to the motor torque
setting.
MG.33.MB.02 - VLT
6-70 Terminal X45/1 Output
Option:
motor
torque
0-20mA
[106] Power
Taken from 1-20 Motor Power [kW].
0-20mA
[107] Speed
Taken from 3-03 Maximum Reference. 20mA =
0-20mA
value in 3-03 Maximum Reference
[108] Torque ref.
Torque reference related to 160% torque.
0-20mA
[109] Max Out
In relation to 4-19 Max Output Frequency.
Freq
0-20mA
[130] Output freq.
0hz = 4mA, 100hz = 20mA
4-20mA
[131] Reference
3-00 Reference Range [Min-Max] 0% = 4mA;
4-20mA
100% = 20mA
3-00 Reference Range [-Max-Max] -100% =
4mA; 0% = 12mA; +100% = 20mA
[132] Feedback
4-20mA
[133] Motor cur.
Value is taken from 16-37 Inv. Max. Current.
4-20mA
Inverter max. current (160% current) is equal
to 20mA.
Example: Inverter norm current (11kW) = 24 A.
160% = 38.4 A. Motor norm current = 22 A
Read-out 11.46mA.
16
In case the norm motor current is equal to
20mA, the output setting of 6-52 Terminal 42
Output Max Scale is:
I VLT
[134] Torque%
The torque setting is related to setting in
lim. 4-20mA
4-16 Torque Limit Motor Mode.
[135] Torque%
The torque setting is related to the motor
nom
torque setting.
4-20mA
[136] Power
Taken from 1-20 Motor Power [kW]
4-20mA
[137] Speed
Taken from 3-03 Maximum Reference. 20mA =
4-20mA
Value in 3-03 Maximum Reference.
[138] Torque
Torque reference related to 160% torque.
4-20mA
[139] Bus ctrl.
An output value set from fieldbus process
0-20mA
data. The output will work independently of
internal functions in the frequency converter.
[140] Bus ctrl.
An output value set from fieldbus process
4-20mA
data. The output will work independently of
internal functions in the frequency converter.
[141] Bus ctrl.
4-54 Warning Reference Low defines the
0-20mA,
behaviour of the analog output in case of bus
timeout
time-out.
®
is a registered Danfoss trademark
Function:
mA x 22 A
= 9.17
mA
38.4
A
x 100
Max
38.4
x 100
=
= 175 %