Parameter Descriptions
6-50 Terminal 42 Output
Option:
Function:
[101] Reference
3-00 Reference Range [Min - Max] 0% = 0mA;
100% = 20mA
3-00 Reference Range [-Max - Max] -100% =
0mA; 0% = 10mA; +100% = 20mA
[102] Feedback
[103] Motor
Value is taken from 16-37 Inv. Max. Current.
current
Inverter max. current (160% current) is equal to
20mA.
Example: Inverter norm current (11kW) = 24A.
160% = 38.4A. Motor norm current = 22A
Read-out 11.46mA.
20
mA x 22 A
A
38.4
In case the norm motor current is equal to
20mA, the output setting of 6-52 Terminal 42
Output Max Scale is:
I VLT
x 100
Max
I Motor
Norm
[104] Torque rel
The torque setting is related to setting in
to limit
4-16 Torque Limit Motor Mode
[105] Torq relate
The torque is related to the motor torque
to rated
setting.
[106] Power
Taken from 1-20 Motor Power [kW].
[107] Speed
Taken from 3-03 Maximum Reference. 20mA =
value in 3-03 Maximum Reference
[108] Torque
Torque reference related to 160% torque.
[109] Max Out
0Hz = 0mA,4-19 Max Output Frequency = 20mA.
Freq
[113] PID
Clamped
Output
[119] Torque %
lim
[130] Output
0Hz = 4mA, 100Hz = 20mA
freq.
4-20mA
[131] Reference
3-00 Reference Range [Min-Max] 0% = 4mA;
4-20mA
100% = 20mA
3-00 Reference Range [-Max-Max] -100% = 4mA;
0% = 12mA; +100% = 20mA
[132] Feedback
4-20mA
Value is taken from 16-37 Inv. Max. Current.
[133] Motor cur.
4-20mA
Inverter max. current (160% current) is equal to
20mA.
Example: Inverter norm current (11kW) = 24A.
160% = 38.4A. Motor norm current = 22A
Read-out 11.46mA.
mA x 22 A
16
A
38.4
FC 300 Programming Guide
= 11.46
mA
38.4
x 100
=
= 175 %
22
mA = 13.17 mA
+ 4
®
MG.33.MB.02 - VLT
is a registered Danfoss trademark
6-50 Terminal 42 Output
Option:
Function:
In case the norm motor current is equal to
20mA, the output setting of 6-62 Terminal
X30/8 Max. Scale is:
I VLT
x 100
Max
I Motor
Norm
[134] Torq.% lim
The torque setting is related to setting in
4-20 mA
4-16 Torque Limit Motor Mode.
[135] Torq.%
The torque setting is related to the motor
nom 4-20
torque setting.
mA
[136] Power
Taken from 1-20 Motor Power [kW]
4-20mA
[137] Speed
Taken from 3-03 Maximum Reference. 20mA =
4-20mA
Value in 3-03 Maximum Reference.
[138] Torque
Torque reference related to 160% torque.
4-20mA
[139] Bus ctrl.
An output value set from fieldbus process data.
0-20 mA
The output will work independently of internal
functions in the frequency converter.
[140] Bus ctrl.
An output value set from fieldbus process data.
4-20 mA
The output will work independently of internal
functions in the frequency converter.
[141] Bus ctrl
4-54 Warning Reference Low defines the
0-20mA t.o.
behaviour of the analog output in case of bus
time-out.
[142] Bus ctrl
4-54 Warning Reference Low defines the
4-20mA t.o.
behaviour of the analog output in case of bus
time-out.
[149] Torque %
Analogue output at zero torque = 12mA.
lim 4-20mA
Motoric torque will increase the output current
to max torque limit 20mA (set in 4-16 Torque
Limit Motor Mode).
Generative torque will decrease the output to
torque limit Generator Mode (set in
4-17 Torque Limit Generator Mode)
Ex: 4-16 Torque Limit Motor Mode: 200% and
4-17 Torque Limit Generator Mode: 200%. 20mA
= 200% Motoric and 4mA = 200% Generatoric.
0mA
4mA
Par 4-17
(200%)
[150] Max Out Fr
0hz = 0mA,4-19 Max Output Frequency = 20mA.
4-20mA
x 100
38.4
=
= 175 %
22
12 mA
20 mA
0% Torque
Par 4-16
(200%)
91
3