Vvw Vector Control Parameterization - WEG CFW501 V1.8X Programming Manual

Frequency inverter
Table of Contents

Advertisement

10.1 VVW VECTOR CONTROL PARAMETERIZATION

The V V W control mode is selected by parameter P0202, control mode selection, as described in
AVAILABLE MOTOR CONTROL TYPES on page
Opposite to the V/f scalar control, the V V W control requires a series of data from the motor nameplate and a
self-tuning for its proper operation. Besides, it is recommended that the driven motor match the inverter, that is,
the motor and inverter power be as close as possible.
The V V W control setting process is simplified by the HMI "STARTUP" menu, where the relevant parameters for
the configuration of the V V W are selected for browsing the HMI.
Below are described the parameters to configure the V V W vector control setting. Those data are easily obtained
on the nameplate of WEG motors; however, in old motors or motor of other manufacturers, this information may
not be available. In those cases, it is recommended first contact the motor manufacturer, measure or calculate the
desired parameter, or, still, make a relationship with
on page 10-3
and use the equivalent or approximate WEG standard motor parameter.
NOTE!
The correct setting of the parameters directly contributes to the V V W control performance.
Power [P0404]
Frame
(CV)
(kW)
0.16
0.12
63
0.25
0.18
63
0.33
0.25
63
0.50
0.37
71
0.75
0.55
71
1.00
0.75
80
1.50
1.10
80
2.00
1.50
90S
3.00
2.20
90L
4.00
3.00
100L
5.00
3.70
100L
6.00
4.50
112M
7.50
5.50
112M
10.0
7.50
132S
12.5
9.20
132M
0.16
0.12
63
0.25
0.18
63
0.33
0.25
63
0.50
0.37
71
0.75
0.55
71
1.00
0.75
80
1.50
1.10
80
2.00
1.50
90S
3.00
2.20
90L
4.00
3.00
100L
5.00
3.70
100L
6.00
4.50
112M
7.50
5.50
112M
10.0
7.50
132S
12.5
9.20
132M
15.0
11.0
132M
20.0
15.0
160M
8-1.
Table 10.1: Characteristics of IV pole WEG standard motors
Table 10.1: Characteristics of IV pole WEG standard motors
Voltage
Current
Frequency
[P0400]
[P0401]
[P0403]
(V)
(A)
(Hz)
0.85
1.12
1.42
2.07
2.90
3.08
4.78
220
6.47
60
8.57
11.6
13.8
16.3
20.0
26.6
33.0
0.49
0.65
0.82
1.20
1.67
1.78
2.76
3.74
380
4.95
60
6.70
7.97
9.41
11.49
15.18
18.48
22.7
30.0
V V W Vector Control
Speed
Efficiency
Power
[P0402]
[P0399]
Factor
(rpm)
(%)
[P0407]
1720
56.0
0.66
1720
64.0
0.66
1720
67.0
0.69
1720
68.0
0.69
1720
71.0
0.70
1730
78.0
0.82
1700
72.7
0.83
1720
80.0
0.76
1710
79.3
0.85
1730
82.7
0.82
1730
84.6
0.83
1730
84.2
0.86
1740
88.5
0.82
1760
89.0
0.84
1755
87.7
0.86
1720
56.0
0.66
1720
64.0
0.66
1720
67.0
0.69
1720
68.0
0.69
1720
71.0
0.70
1730
78.0
0.82
1700
72.7
0.83
1720
80.0
0.76
1710
79.3
0.85
1730
82.7
0.82
1730
84.6
0.83
1730
84.2
0.86
1740
88.5
0.82
1760
89.0
0.84
1755
87.7
0.86
1755
88.5
0.83
1760
90.2
0.83
chapter 8
Stator
Resistance
[P0409] (Ω)
21.77
14.87
10.63
7.37
3.97
4.13
10
2.78
1.55
0.99
0.65
0.49
0.38
0.27
0.23
0.16
65.30
44.60
31.90
22.10
11.90
12.40
8.35
4.65
2.97
1.96
1.47
1.15
0.82
0.68
0.47
0.43
0.23
CFW501 | 10-3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents