14.16 FAULT AUTO-RESET
This function allows the inverter to execute the automatic reset of a fault by means of the setting of P0340.
NOTE!
The auto-reset is locked if the same fault occurs three times in a row within 30 seconds after the reset.
P0340 – Auto-Reset Time
Adjustable
0 to 255 s
Range:
Description:
It defines the interval after a fault to activate the inverter auto-reset. If the value of P0340 is zero the fault
auto-reset function is disabled.
Faults and Alarms
Factory
0 s
Setting:
CFW501 | 14-11