P0220 – Local/Remote Selection
Adjustable
0 = Always Local
Range:
1 = Always Remote
2 = Local / Remote HMI Key (LOC)
3 = Local / Remote HMI Key (REM)
4 = Digital Input (DIx)
5 = Serial / USB (LOC)
6 = Serial / USB (REM)
7 = SoftPLC
Properties:
cfg
Access groups
I/O
via HMI:
Description:
It defines the command origin source which will select between Local situation and Remote situation, where:
LOC: means Local situation default.
REM: means Remote situation default.
DIx: according to function programmed for digital input in P0263 to P0270.
P0221 – Speed Reference Selection – LOCAL Situation
P0222 – Speed Reference Selection – REMOTE Situation
Adjustable
0 = HMI Keys
Range:
1 = AI1
2 = AI2
3 = AI3
4 = AI1 + AI2 > 0 (Sum AIs > 0)
5 = AI1 + AI2 (Sum AIs)
6 = Serial / USB
7 = SoftPLC
8 = Frequency input (FI)
9 = AI1 > 0
10 = AI2 > 0
11 = AI3 > 0
12 = FI > 0
Properties:
cfg
Access groups
I/O
via HMI:
Description:
These parameters define the origin source for the speed reference in the Local situation and Remote situation.
Some comments on the options of this parameter:
AIx: it refers to the analog input signal according to
HMI: the reference value set by the keys and contained in parameter P0121.
AIx > 0: the negative values of the AIx reference are zeroed.
Logical Command and Speed Reference
section 12.1 ANALOG INPUTS on page
Factory
2
Setting:
Factory
P0221 = 0
Setting:
P0222 = 1
12-1.
CFW501 | 7-5
7