WEG CFW501 V1.8X Programming Manual page 192

Frequency inverter
Table of Contents

Advertisement

HVAC Functions
P0583 – Mode Configuration "Bypass"
Adjustable
Range:
Properties:
Access groups
via HMI:
Description:
This parameter configured the triggering event for the CFW501 entering the Bypass Mode.
P0584 – Bypass Contactor Time
Adjustable
Range:
Properties:
Access groups
via HMI:
Description:
This parameter defines the delay between the opening of one contactor and the closing of the other contactor.
18
18-34 | CFW501
0 = Inactive
1 = Active/DIx
2 = Active/DIx+Failure
cfg
HVAC
Table 18.14: Options for the parameter P0583
P0583
0
Bypass mode is always disabled.
1
Bypass mode is enabled by a digital input (DIx) set to "Bypass".
2
Bypass mode is enabled either by a digital input (DIx) set to "Bypass" or
when a fault happens.
0.00 to 300.00 s
cfg
HVAC
Factory
Setting:
Description
Factory
Setting:
0
0.30 s